Plan Review Notes For Permit 12040202 |
Permit Number |
12040202 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-04-30 15:22:15 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 2ND REVIEW: | | | | 1. OK | | | | 2. APPLICATION IS FOR WINDOWS AND DOORS, PLAN SHOWS | | INTERIOR REPAIRS. PLEASE CORRELATE BY EITHER REVISING | | APPLICATION TO REFLECT WORK ON PLAN OR REVISE PLAN TO | | REMOVE WORK OTHER THAN WINDOWS/DOORS. | | | | 2ND REVIEW, PLAN CORRECTED, UPDATE VALUE TO INCLUDE | | DRYWALL AND SHUTTERS. | | | | 3. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS | | ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE | | (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM | | /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF) ***TWO | | SETS REQUIRED*** | | | | IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4, | | PROVIDE CALCULATIONS. | | | | SHUTTER PRODUCT APPROVALS PROVIDED, PLEASE COMPLETE THE | | INSTALLATION SCHEDULE. | | | | 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. VALUE | | TO INCLUDE MATERIALS AND LABOR. | | | | CONTRACT PROVIDED, INCREASE VALUE TO INCLUDE SHUTTERS | | AND DRYWALL. | | | | |
|