2012-04-10 15:00:14****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. BLOCK SUBSTRATE, 58.6 PSF, REQUIRES 8" ANCHOR
 SPACING, SEE CHART ON SHEET 11.
  
 PLEASE SEE INSTALLATION SHEDULE AND ENGINEERING. ZONE 4
 10SF PRESSURE OF -47.4 WAS CIRCLED, AND ZONE 5 10SF
 PRESSURE OF -58.6 WAS CIRCLED. FOR DESIGN PRESSURE ON
 THE INSTALLATION SCHEDULE, +47.4/-58.6 WAS PROPOSED.
 NOT CLEAR WHAT INTENT WAS; PLEASE FEEL FREE TO CONTACT
 ME IF YOU NEED ASSISTANCE.
  
  
  