Plan Review Notes
Plan Review Notes For Permit 12040135
Permit Number 12040135
Review Stop B
Sequence Number 2
Notes
Date Text
2012-06-06 06:56:25****PROVISO****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENT FROM FIRST REVIEW:
  
 1. GOVERNING CODE CHANGED ON 3/15/12, FS 553. IT IS NOT
 CLEAR WHY THE ENGINEER SIGNED AND SEALED THE PLAN WITH
 A DATE OF 3/19/12. PLEASE REVISE.
  
 2ND REVIEW:
  
 COMMENT NOT ADDRESSED. GOVERNING CODE IS FBC 2010,
 FS553. DESIGN IS TO BE DONE ACCORDING TO ASCE7-10 PER
 FBC CHAPTER 35, FBC 1609.1.1. THE PLAN IS DATED
 3/19/12, AND THE APPLICATION IS DATED 4/5/12. THE PLAN
 WAS SIGNED AND SEALED AS COMPLIANT WITH FBC 2007 AND
 ASCE7-05, NOT COMPLIANT FOR THE CURRENT CODE.
  
 ***THIS PERMIT IS ISSUED WITH PROVISO, REVISION
 REQUIRED PRIOR TO FIRST INSPECTION***
 ***ISSUED AT CONTRACTOR'S RISK****
  
 REVISE PLAN TO INCLUDE CORRECT GOVERNING CODE AND
 CORRECT ASCE7 REFERENCE.
  
  
  