Date |
Text |
2012-04-12 14:32:47 | 501 FERN STREET |
| PERMIT #12040122 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| CONSTRUCTION AND DEMOLITION ACTIVITIES SHALL COMPLY |
| WITH THE 2010 EDITION OF THE FLORIDA FIRE PREVENTION |
| CODE WHICH CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND |
| NFPA 101 WITH FLORIDA AMENDMENTS. |
| |
| ALL DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| SMOKING" SIGNS POSTED. |
| |
| PLANS REFERENCE TWO SHEETS THAT WERE NOT PROVIDED |
| (SHEET 1A-1 AND SHEET 1A-2). |
| |
| PROVIDE A LIFE SAFETY PLAN INDICATING EXIT DOORS, FIRE |
| RATED DOORS AND WALLS, PORTABLE FIRE EXTINGUISHERS, |
| EXIT SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, |
| COMMON PATH OF TRAVEL ETC. |
| |
| PLAN NOTE 71 INDICATES FIRE SPRINKLERS AND EQUIPMENT TO |
| BE RELOCATED. NO ENGINEERING DRAWINGS WERE PROVIDED |
| SHOWING THIS SCOPE OF WORK. |
| |
| FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| |
| SHEET E-1: BUILDINGS LABELS "A" AND "B" ARE SWITCHED |
| WHEN COMPARED TO OTHER SHEETS. THIS SHEET SHOWS ONLY |
| ONE EXIT FOR EACH BUILDING. |
| |
| WESLEY JOLIN |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| |