Plan Review Notes
Plan Review Notes For Permit 12040122
Permit Number 12040122
Review Stop B
Sequence Number 1
Notes
Date Text
2012-04-12 07:42:08BUILDING PLAN REVIEW
 PERMIT: 12040122
 ADD: 501 FERN ST SUITE B
 CONT: AUTOBUILDERS
 TEL: (561)722-3956
  
 2010FLORIDA BUILDING CODE W
 * WEST PALM BEACH AMENDMENTS
 S-2 OCCUPANCY
 BUILDING TYPE: IIIB
 SPRINKLERED
  
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS 1A-3 DO NOT INDICATE TO WHAT EDITION OF CODE
 THE PLANS WERE DESIGNED TOO? ADMINISTRATIVE CODE
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR PLAN REVIEW.
  
 2) PLANS S-2 DO NOT INDICATE THE WIND DESIGN CRITERIA
 NOR THE WIND SPEED THIS BUILDING WAS DESIGNED TOO? 2010
 FBC-B 1609.1.1.
 1609.6.2 WIND DESIGN PROCEDURES
 2.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
 2.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
 2.5) WALL PRESSURES POSITIVE & NEGATIVE
  
 3) SHEET 1A-3 BUILDING DATA INDICATES THIS IS A TYPE
 III-B FULLY SPRINKLERED BUILDING, BUT NOTE # 16
 INDICATES FIRE SPRINKLER WORK TO BE COMPLETED BY THE
 FUTURE TENANT. WHAT IS THE TOTAL SQ FT OF THE BUILDING?
 ARE AREA INCREASES FOR SPRINKLERS BEING TAKEN? IS THIS
 SYSTEM A FULLY FUNCTIONAL SYSTEM?
  
 4) SHEET R-1, IS THE TOTAL SQ FT OF THE BUILDING TO BE
 CONSIDERED A S-2 OCCUPANCY OR ISTHIS A MIXED USE
 OCCUPANCY? PLANS DO NOT INDICATE IF THE WALL BETWEEN
 WAREHOUSE A & B SHALL BE A TENANT SEPERATION WALL OR IF
 IT MAY REQUIRED TO BE A OCCUPANCY SEPERATION WALL? 2010
 FBC-B ADMINISTRTIVE CODE 106.3.5 MINIMUM PLAN REVIEW
 CRITERIA.
  
 5) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6) MISSING PRODUCT APPROVALS
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 7) PLEASE BE AWARE OF MIAMI-DADE NOA DECK LIMITATIONS
 FOR SPANS BETWEEN BAR JOIST SEE DECK LIMITATION # 2
 DECK SPANS EVERY 5 FT. THE CURRENT SHEET S-2 BAR JOIST
 SPACING DOES EXCEED 5'-0" ON CENTER, THIS MAY DEPEND ON
 THE GUAGE OF SHEET METAL DECKING TO BE INSTALLED!
 BEWARE.106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 8) S-2 INDICATES WHAT APPEARS TO BE ROOF FRAMING FOR
 ROOF TOP PACKAGE UNITS PLEASE PROVIDE CURB INFORMATION
 AND ANCHORAGE FOR THE CURBS. IF PACKAGE UNITS ARE TO BE
 INCORPORATED INTO THIS PERMIT PLEASE PROVIDE ANCHORAGE
 TO CURB. FBC-B 1609. COMPONENTS & CLADDING.
  
 9) SHEET S-3 INDICATES ROOF TOP ELEVATIONS ABOVE 16
 FEET BE AWARE OF 2010 FBC-M 306.5 WHERE EQUIPMENT AND
 APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR
 ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877
 MM), SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT
 APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE
 FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND
 APPLIANCES' LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES (762 MM) HIGH.
  
 10) 1013.5 MECHANICAL EQUIPMENT. GUARDS SHALL BE
 PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS, ROOF HATCH
 OPENINGS OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE
 LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN
 SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS
 LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR,
 ROOF OR GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO
 AS TO PREVENT THE PASSAGE OF A 21-INCH-DIAMETER (533
 MM) SPHERE. THE GUARD SHALL EXTEND NOT LESS THAN 30
 INCHES (762 MM) BEYOND EACH END OF SUCH APPLIANCE,
 EQUIPMENT, FAN OR COMPONENT.
  
 11) 1013.6 ROOF ACCESS. GUARDS SHALL BE PROVIDED WHERE
 THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET (3048
 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE
 AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN 30
 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW.
 THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE
 PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE.
  
 12) CONTRACTOR TO COME IN BEFORE ISSUANCE OF PERMT TO
 INDICATE UNDER SCOPE OF WORK ON THE PERMIT APPLICATION
 "SHELL ONLY".
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  