Plan Review Notes For Permit 12040098 |
Permit Number |
12040098 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-04-04 17:07:23 | RESIDENTIAL (R2) RE-ROOF BUILDING REVIEW COMMENTS. | | 2010 FBC. | | | | ***NOTE: USING THIS PERMIT APPLICATION AS MASTER FOR | | ALL RE-ROOF PERMITS WITH IDENTICAL DESCRIPTION. PLEASE | | PROVIDE THREE COMPLETE PACKAGES. ONE APPROVED PACKAGE | | WILL STAY IN OUR FILE AND THE OTHER TWO WILL BE GIVEN | | TO THE CONTRACTOR TO BE USED IN THE FIELD. | | | | 1- THE FBC 2010 WENT INTO EFFECT ON MARCH 15, 2012. | | ENGINEER NEEDS TO UPDATE/REVISE THE RAS 117 | | CALCULATIONS USING THE 2010 FBC. | | | | 2- FOR YOUR INFORMATION FLAT ROOF NOA 07-1018.10 | | SUBMITTED EXPIRES THIS YEAR ON AUGUST 22, 2012. THAT | | MEANS THAT THIS MASTER WILL BE VOID AFTER THAT DATE AND | | A NEW MASTER WILL BE REQUIRED. | | | | 3- PLEASE PROVIDE A FIELD WITHDRAWAL RESISTANCE TEST | | (TAS 105) AS REQUIRED BY GENERAL LIMITATION #5 ON LAST | | PAGE OF NOA SUBMITTED. | | | | ***NOTE: IF THE FIELD TESTED VALUE OF THE FASTENER IS | | LESS THAN 275 LBF, THEN INSULATION ATTACHMENT SHALL NOT | | BE ACCEPTABLE. SEE GENERAL LIMITATION #5. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|