2012-10-11 08:57:59 | BUILDING PLAN REVIEW |
| PERMIT:12040085 |
| ADD: 4312 PINEWOOD |
| CONT: ANCHOR GENERAL CONTRACTING |
| TEL: (561)386-1266 |
| |
| 2010 FLORIDA BUILDING CODE- RESIDENTIAL W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| RESIDENTIAL PLUMBING |
| OCT. 11/2012 |
| 3RD REVIEW |
| |
| NOTE SAME PLANS AS SUBMITTED FOR 2ND REVIEW DATED |
| 5/15/12 |
| NOTE: |
| CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A |
| LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE |
| FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED THREE |
| OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A CODE |
| VIOLATION. |
| |
| 1) THE PLUMBING ISOMETRIC FOR WASTE IS DRAWN |
| INCORRECTLY: |
| 1A) HAND DRAWN IS INDICATED A SECOND SINK, THERE IS |
| ONLY ONE SINK SHOWN ON THE FLOOR PLAN, WHAT IS |
| MISLABLED IS THE HAND DRAWN SINK, IT IS PROBABLY THE |
| MISSING LAVATORY. |
| 2010 FBC-R 3108.1. |
| 1B) THE PLUMBING RISER HAS THE KITCHEN SINK TYING IN |
| BEFORE THE WET VENT IT SHOULD TIE INTO THE MAIN |
| BUILDING DRAIN AFTER THE WET VENT. |
| 2010 FBC-R 3108.1. |
| 1C) THE STACK AS DRAWN IS DIRECTLY BEHIND THE SINK |
| WHICH WOULD PLACE IT DIRECTLY IN THE MIDDLE OF THE |
| WINDOW, IT SHOULD BE ON ONE SIDE OF THE WINDOW. |
| 107.3.5 MINIMUM CRITERIA PLAN REVIEW. |
| 2) NO INFORMATION WAS PROVIDED ON THE PLUMBING AND |
| SAFETY DEVICES FOR THE WATER HEATER. |
| 2010 FBC-R 2805.1 PAN REQUIRED/ P2803.1 & 2803.6.1 |
| REQUIREMENTS FOR DISCHARGE PIPE. |