Plan Review Notes For Permit 12040085 |
Permit Number |
12040085 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2012-12-12 14:59:14 | *** MECHANICAL CORRECTIONS NEEDED *** | | | | NOTE: AS THE PREVIOUS WORK WAS DONE WITHOUT A PERMIT | | ALL MECHANICAL MUST BE INSPECTED. | | | | 1) SUBMIT ENERGY CALCULATIONS, PER 2010 FBC/ENERGY | | 401.3. | | | | 2) SUBMIT MECHANICAL PLANS SHOWING INFORMATION | | REGARDING AIR HANDLER UNIT, CONDENSER UNIT, AND DUCT | | WORK. STATE ON PLANS IF IT IS NEW OR EXISTING AND | | SHOWING IF THE AHU AND C/U ARE COMPATIBLE TO MEET THE | | REQUIRED SEER. CITY OF WPB AMEND. 107.3.5.3 (10). | | | | 3) SHOW THE SIZE OF THE BATHROOM WINDOW TO SHOW IF AN | | EXHAUST FAN IS NEEDED, SEE 2010 FBC/R M1507.1. | | | | 4) THE COOLING LOAD CALCULATIONS SUBMITTED STATES ONLY | | ONE TON OF A/C IS NEEDED, A COMMENT CAN NOT BE MADE AT | | THIS TIME AS THE SIZE OF THE A/C SYSTEM IS NOT KNOW. | | | | *** MECHANICAL PLAN REVIEW BY: TOM GORDON (HY-BYRD | | INC.) | | *** FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710 |
|