2012-10-11 08:46:39 | BUILDING PLAN REVIEW |
| PERMIT:12040085 |
| ADD: 4312 PINEWOOD |
| CONT: ANCHOR GENERAL CONTRACTING |
| TEL: (561)386-1266 |
| |
| 2010 FLORIDA BUILDING CODE- RESIDENTIAL W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 3RD REVIEW |
| OCT. 11/2012 |
| ACTION: DENIED |
| |
| NOTE: PLANS DATED FROM 5/15/2012 ARE PLANS FROM 2ND |
| REVIEW, NO ADDITIONAL PLANS WERE SUBMITED!!!!!! |
| |
| BUILDING: |
| 1) SEMI-COMPLIED. CHANGE OF OCCUPANCY FROM GARAGE |
| UTILTY R-3 AN EFFICENCY UNIT. |
| |
| 2) COMPLIED.2 |
| |
| 3) 2ND REQUEST.CHANGE OF OCCUPANCY SCOPE OF WORK HAS |
| CHANGED, THE VALUE OF THE PROJECT IS TO LOW PER CITY |
| AMENDMENTS 109.3 VALUE NEEDS TO BE ADJUSTED TO REFLECT |
| PROPOSED WORK TO BE COMPLETED UNDER THIS PERMIT. WPB |
| ADMINISTRATIVE CODE. 109.3 BUILDING PERMIT VALUATIONS. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT |
| SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW |
| DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED |
| CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL |
| OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING |
| ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE |
| LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST |
| ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS |
| PUBLISHED BY INTERNATIONAL CODE CONGRESS. FINAL |
| BUILDING PERMIT VALUATION SHALL BE SET BY THE BUILDING |
| OFFICIAL. |
| |
| 4) COMPLETED. |
| |
| 5) 3RD REQUEST, APPLICABLE CODES, A CHANGE OF OCCUPANCY |
| IS NOT A LEVEL 3 ALTERATION PLEASE REVIEW 2010 EXST |
| BLDG CODE CHAPTER 9 SECTION 901.3, WHEN A CHANGE OF |
| OCCUPANCY OCCURS FOR THE FULL BUILDING THEN SECTION 902 |
| THROUGH 912 SHALL APPLY. |
| |
| 6) 3RD REQUEST, PROVIDE A WIND LOAD ANALYSIS OF THE |
| EXISTING STRUCTURE TO SHOW COMPLIANCE WITH THE |
| APPLICABLE WIND LOAD PROVISIONS OF THE FLORIDA BUILDING |
| CODE AS REQUIRED BY EXST BLDG CODE 907.2. |
| |
| 7) 3RD REQUEST, SUBMIT A STRUCTURAL DETAIL OF THE |
| IN-FILL WALL AT TTHE GARGE OPENING PER CITY AMENDMENT |
| 107.2.1.3. DISCREPANCY IN PLANS, SHEET A-1 INDICATES |
| WOOD INFILL PEN SCRATCHED OUT, WHEREAS A2 SECTION B |
| INDICATES CBS CONSTRUCTION DETAIL ON A2 INDICATES WOOD |
| INFILL. |
| |
| 8-12) COMPLIED. |
| |
| 13) 3RD REQUEST, WITH THE BATHROOM ONLY BEING 4'-0" |
| WIDE IT IS QUESTIONABLE IF THERE WILL BE 21" IN FRONT |
| OF THE WATER CLOSET PER FBC-R 307.1. |
| |
| 14-15) COMPLIED. |
| |
| 16) SHOW COMPLIANCE WITH R303.8 FOR REQUIRED HEATING. |
| |
| 17) COMPLIED. |
| |
| 18) COMPLIED. |
| |
| 19) SHOW COMPLIANCE WITH FBC ENERGY CONVERSATION |
| 101.4.1 & 101.4.5. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| NOTE: |
| CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A |
| LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE |
| FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED THREE |
| OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A CODE |
| VIOLATION. |