Plan Review Notes
Plan Review Notes For Permit 12040085
Permit Number 12040085
Review Stop B
Sequence Number 3
Notes
Date Text
2012-10-11 08:46:39BUILDING PLAN REVIEW
 PERMIT:12040085
 ADD: 4312 PINEWOOD
 CONT: ANCHOR GENERAL CONTRACTING
 TEL: (561)386-1266
  
 2010 FLORIDA BUILDING CODE- RESIDENTIAL W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 3RD REVIEW
 OCT. 11/2012
 ACTION: DENIED
  
 NOTE: PLANS DATED FROM 5/15/2012 ARE PLANS FROM 2ND
 REVIEW, NO ADDITIONAL PLANS WERE SUBMITED!!!!!!
  
 BUILDING:
 1) SEMI-COMPLIED. CHANGE OF OCCUPANCY FROM GARAGE
 UTILTY R-3 AN EFFICENCY UNIT.
  
 2) COMPLIED.2
  
 3) 2ND REQUEST.CHANGE OF OCCUPANCY SCOPE OF WORK HAS
 CHANGED, THE VALUE OF THE PROJECT IS TO LOW PER CITY
 AMENDMENTS 109.3 VALUE NEEDS TO BE ADJUSTED TO REFLECT
 PROPOSED WORK TO BE COMPLETED UNDER THIS PERMIT. WPB
 ADMINISTRATIVE CODE. 109.3 BUILDING PERMIT VALUATIONS.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT
 SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL
 OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST
 ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS
 PUBLISHED BY INTERNATIONAL CODE CONGRESS. FINAL
 BUILDING PERMIT VALUATION SHALL BE SET BY THE BUILDING
 OFFICIAL.
  
 4) COMPLETED.
  
 5) 3RD REQUEST, APPLICABLE CODES, A CHANGE OF OCCUPANCY
 IS NOT A LEVEL 3 ALTERATION PLEASE REVIEW 2010 EXST
 BLDG CODE CHAPTER 9 SECTION 901.3, WHEN A CHANGE OF
 OCCUPANCY OCCURS FOR THE FULL BUILDING THEN SECTION 902
 THROUGH 912 SHALL APPLY.
  
 6) 3RD REQUEST, PROVIDE A WIND LOAD ANALYSIS OF THE
 EXISTING STRUCTURE TO SHOW COMPLIANCE WITH THE
 APPLICABLE WIND LOAD PROVISIONS OF THE FLORIDA BUILDING
 CODE AS REQUIRED BY EXST BLDG CODE 907.2.
  
 7) 3RD REQUEST, SUBMIT A STRUCTURAL DETAIL OF THE
 IN-FILL WALL AT TTHE GARGE OPENING PER CITY AMENDMENT
 107.2.1.3. DISCREPANCY IN PLANS, SHEET A-1 INDICATES
 WOOD INFILL PEN SCRATCHED OUT, WHEREAS A2 SECTION B
 INDICATES CBS CONSTRUCTION DETAIL ON A2 INDICATES WOOD
 INFILL.
  
 8-12) COMPLIED.
  
 13) 3RD REQUEST, WITH THE BATHROOM ONLY BEING 4'-0"
 WIDE IT IS QUESTIONABLE IF THERE WILL BE 21" IN FRONT
 OF THE WATER CLOSET PER FBC-R 307.1.
  
 14-15) COMPLIED.
  
 16) SHOW COMPLIANCE WITH R303.8 FOR REQUIRED HEATING.
  
 17) COMPLIED.
  
 18) COMPLIED.
  
 19) SHOW COMPLIANCE WITH FBC ENERGY CONVERSATION
 101.4.1 & 101.4.5.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 NOTE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED THREE
 OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A CODE
 VIOLATION.