2012-07-06 16:58:17 | BUILDING PLAN REVIEW |
| PERMIT:12040085 |
| ADD: 4312 PINEWOOD |
| CONT: ANCHOR GENERAL CONTRACTING |
| TEL: (561)386-1266 |
| |
| 2010 FLORIDA BUILDING CODE- RESIDENTIAL W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| BUILDING: |
| 1) CHANGE OF OCCUPANCY FROM GARAGE UTILTY R-3 AN |
| EFFICENCY UNIT. |
| |
| 2) 2ND REQUEST, CONTRACTOR TO CHANGE SCOPE OF WORK ON |
| THE PERMIT APPLICATION TO INCLUDE " CHANGE OF |
| OCCUPANCY". |
| |
| 3) 2ND REQUEST.CHANGE OF OCCUPANCY SCOPE OF WORK HAS |
| CHANGED, THE VALUE OF THE PROJECT IS TO LOW PER CITY |
| AMENDMENTS 109.3 VALUE NEEDS TO BE ADJUSTED TO REFLECT |
| PROPOSED WORK TO BE COMPLETED UNDER THIS PERMIT. |
| WPB ADMINISTRATIVE CODE. 109.3 BUILDING PERMIT |
| VALUATIONS. IF, IN THE OPINION OF THE BUILDING |
| OFFICIAL, THE CLAIMED VALUATION OF |
| BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED, UNLESS THE APPLICANT CAN SHOW |
| DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED |
| CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE |
| APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL |
| BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING |
| ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE |
| LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION |
| COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), |
| AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. |
| FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| BUILDING OFFICIAL. |
| |
| 4) COMPLETED. |
| |
| 5) 2ND REQUEST, APPLICABLE CODES, A CHANGE OF OCCUPANCY |
| IS NOT A LEVEL 3 ALTERATION PLEASE REVIEW 2010 EXST |
| BLDG CODE CHAPTER 9 SECTION 901.3, WHEN A CHANGE OF |
| OCCUPANCY OCCURS FOR THE FULL BUILDING THEN SECTION 902 |
| THROUGH 912 SHALL APPLY. |
| |
| 6) 2ND REQUEST, PROVIDE A WIND LOAD ANALYSIS OF THE |
| EXISTING STRUCTURE TO SHOW COMPLIANCE WITH THE |
| APPLICABLE WIND LOAD PROVISIONS OF THE FLORIDA BUILDING |
| CODE AS REQUIRED BY EXST BLDG CODE 907.2. |
| |
| 7) 2ND REQUEST, SUBMIT A STRUCTURAL DETAIL OF THE |
| IN-FILL WALL AT TTHE GARGE OPENING PER CITY AMENDMENT |
| 107.2.1.3. DISCREPANCY IN PLANS, SHEET A-1 INDICATES |
| WOOD INFILL |
| PEN SCRATCHED OUT, WHEREAS A2 SECTION B INDICATES CBS |
| CONSTRUCTION DETAIL ON A2 INDICATES WOOD INFILL. |
| |
| 8-12) COMPLIED. |
| |
| 13) 2ND REQUEST, WITH THE BATHROOM ONLY BEING 4'-0" |
| WIDE IT IS QUESTIONABLE IF THERE WILL BE 21" IN FRONT |
| OF THE WATER CLOSET PER FBC-R 307.1. |
| |
| 14-15) COMPLIED. |
| |
| 16) SHOW COMPLIANCE WITH R303.8 FOR REQUIRED HEATING. |
| |
| 17) THE CONTRACTOR ELECTED TO USE NON-IMPACT GLAZING, |
| PRODUCT APPROVALS WERE SUBMITTED BUT THE FOLLOWING |
| INFORMATION IS STILL UNKNOWN: |
| PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND |
| MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC |
| 1609.1.4. |
| |
| FL BLD CODE 2004 SECTION 106.3.3, |
| 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY |
| HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT |
| STORM |
| BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT |
| TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT |
| APPLICATION |
| TO FACILITATE PLAN REVIEW AND PERMIT ISSUANCE. |
| |
| 18) COMPLIED. |
| |
| 19) SHOW COMPLIANCE WITH FBC ENERGY CONVERSATION |
| 101.4.1 & 101.4.5. |
| |
| JAMES A. WITMER CBO |