2012-04-23 14:57:0312040085
 4312 PINEWOOD AVE.
 INTERIOR RENOVATION
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 FOR THE NEW WALL SPACES ADD RECEPTACLES SO THAT NO WALL
 SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE AND ALL
 WALL SPACES MORE THAN 2 FEET IN WIDTH HAVE A RECEPTACLE
 I.E. NEW CLOSET WALL. NEC 210.52
 ALL NEW GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE
 BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC
 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG
 THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. NEC 210.52
 THE NEW LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR
 LIGHT AND A SWITCHED LIGHT AT OUTSIDE ENTRANCES. A GFCI
 PROTECTED RECEPTACLE IS REQUIRED OUTSIDE FRONT AND
 BACK. NEC 210.70
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER