Plan Review Notes For Permit 12040070 |
Permit Number |
12040070 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-04-09 13:56:24 | PLAN DENIED | | 1) PROVIDE GRILLE SIZE AND DUCT SIZE ON PLAN. | | 2) REFER TO SECTION M1602.4 BALANCED RETURN AIR | | 2010 FBC (R) | | 3) PROVIDE ENERGY CALCULATION OR MANUAL J WITH THE PLAN | | PER SECTION 403.6.1 EQUIPMENT SIZING.2010 ENERGY CODE. | | 4) REFER TO SECTIONM1305.1.3 APPLIANCE IN ATTIC. | | 2010 FBC (R) | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] | | | | |
|