Plan Review Notes
Plan Review Notes For Permit 12040070
Permit Number 12040070
Review Stop M
Sequence Number 1
Notes
Date Text
2012-04-09 13:56:24PLAN DENIED
 1) PROVIDE GRILLE SIZE AND DUCT SIZE ON PLAN.
 2) REFER TO SECTION M1602.4 BALANCED RETURN AIR
 2010 FBC (R)
 3) PROVIDE ENERGY CALCULATION OR MANUAL J WITH THE PLAN
 PER SECTION 403.6.1 EQUIPMENT SIZING.2010 ENERGY CODE.
 4) REFER TO SECTIONM1305.1.3 APPLIANCE IN ATTIC.
 2010 FBC (R)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  
  