2012-04-23 17:22:3412040044 & 12040042
 1700 WORTHINGTON ROAD
 BLDG. A & B
  
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 VERIFY COMPLIANCE WITH LIGHTING AND GLARE REQUIREMENTS
 FOR CLASS ROOMS. FBC 443.3.7
 PROVIDE A RISER PLAN SHOWING THE NEW AND EXISTING
 ELECTRIC SERVICE COMPONENTS WITH MAIN DISCONNECT,
 SERVICE GROUNDING, CONDUIT SIZE AND TYPE, CONDUCTOR
 SIZE AND TYPE ALL LOCATED ON THE PLAN. INCLUDE A
 SUMMARY LOAD CALCULATION SHOWING EXISTING ELECTRIC
 SERVICE CAN HANDLE THE NEW LOADS; VERIFY SAFETY
 CLEARANCES AND ACCESS. NEC 110.26, 215.5
 PROVIDE AN INTERSYSTEM BONDING TERMINAL. NEC 250.94
 PROVIDE FOR GFCI PROTECTION AT THE VENDING MACHINES.
 NEC 422.51
  
 NOTE:
 SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 ALARM SYSTEM, VOICE AND DATA.
  