2012-04-10 16:21:20 | BUILDING PLAN REVIEW |
| PERMIT: 12040044 |
| ADD: 1711 WORTHINGTON BLDG PHASE I BLDG 100 SUITE 108 |
| BUSINESS |
| CONT: ONICX LLC |
| TEL: (813)964-0666 |
| |
| 2010 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) THE CONTRACTOR IS TO COME IN AND CHANGE THE PERMIT |
| APPLICATION UNDER THE HEADING DESCRIPTION OF WORK. THE |
| PERMIT APPLICATION AND PLANS NEED TO USE THE SAME |
| NOMENCLATURE THE PLANS INDICATE THIS PORTION OF WORK AS |
| PHASE I BLDG 100 BUSINESS L/ CHANGE IN OCCUPANCY. |
| |
| 2) SHEET A-0.0 COVER SHEET & INDEX; |
| 2A) CODE INFORMATION, THE MINIMUM BUILDING TYPE IS NOT |
| PROVIDED ONLY A "B" TYPE 2010 FBC-B WPB ADMINISTRATIVE |
| CODE 106.3.5.1.1(3) MINIMUM TYPE OF CONSTRUCTION & |
| TABLE 503. |
| |
| BUILDING 200 PHASE II THE EDUCATIONAL OCCUPANCY |
| INDICATES AN AREA OF 11,410 SQ FT, PLEASE PROVIDE THE |
| MINIMUM BUILDING TYPE IF AREA INCREASES WERE CONSIDERED |
| FOR FRONTAGE OR FIRE SPRINKLERS FBC-B 506.2 AND OR |
| 506.3. |
| |
| 2B) THE PLANS DO NOT PROVIDE DOCUMENTATION IF THIS |
| BUILDING IS PROTECTED BY NFPA 13 FIRE SPRIKLER SYSTEM |
| OR NOT? INDEX DOES NOT INDICATE ANY FIRE SPINKLER OR |
| FIRE PROTECTION PLANS WITHIN THE SET? 106.3.5.1.1(5) |
| SCHEMATIC FIRE SPRINKLERS. |
| |
| 2C) THE HEADING OF CODE INFORMATION FBC-B 803.5 |
| INDICATES, CLASS B FOR EXITS & CORRIDORS/ CLASS C FOR |
| ROOMS AND ENCLOSED SPACES THESE RATINGS ARE FOR FIRE |
| SPRINKLERED BUILDINGS. |
| |
| 2D) THE COVER SHEET ALSO INDICATES THE USE OF YKK |
| YES40F1 WINDOW PRODUCT APPROVALS FL 7606.1 PLEASE NOTE |
| THIS REPORT IS FOR NON- MISSILE RATED GLAZING WHICH |
| WILL REQUIRE PRODUCT TESTING REPORT FOR STORM PANELS. |
| |
| THE OTHER ISSUE WITH THE SUBMITTED FL 7606.1 REPORT |
| ONLY THE COVER SHEETS WERE UPLOADED, THE ACTUAL |
| EVALUATION REPORT WITH PRESSURES WAS NOT INCLUDED NOR |
| WAS THE INSTALATION INSTRUCTIONS THAT TIE TO THE |
| FLORIDA COVER SHEET. |
| |
| PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND |
| MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC |
| 1609.1.4. |
| |
| FL BLD CODE 2004 SECTION 106.3.3, |
| 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE |
| SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS, |
| UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR |
| REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT |
| TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT |
| APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE. |
| |
| 2E) THE SECOND PRODUCT APPROVAL THE COVER SHEET LISTED |
| IS FOR EXTERIOR OUTSWING YKK DOOR FL 9967.1 NO REPORT |
| WAS FOUND UNDER THIS PRODUCT NUMBER. |
| |
| 3) SHEET A-1.0: |
| 3A) PLEASE PROVIDE THE DISTANCE BETWEEN THE TWO |
| BUILDINGS AND PROVIDE COMPLIANCE WITH FBC-B TABLE 602 |
| OR ARE THEY CONSIDERED BUILDINGS ON SAME LOT UNDER |
| FBC-B 503.1.2. |
| |
| 3B) THE PLANS DO NOT COMMENT ON THE TENANT SEPERATION |
| WALL BETWEEN THE BUSINESS OCCUPANCY AND THE NEXT TENANT |
| SPCACE, OR IS THIS ALSO A OCCUPANCY SEPERATION WALL? |
| FBC-B 709.6 / TABLE 508.4? |
| |
| 4) SHEET A-2.0 FILE ROOM 104 WALL TYPE 4 INDICATES A 2 |
| HR WALL BUT THE WALL DOES NOT GO TO THE ROOF DECK |
| ABOVE. THE DESIGNER HAS ELECTED TO PROVIDE A FIRE RATED |
| CEILING BUT NO ASSEMBLY HAS BEEN PROVIDED FOR THE RATED |
| CEILING AS THE WALL. FBC-B TABLE 508.4 & 707.3.9. |
| |
| 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |