Plan Review Notes
Plan Review Notes For Permit 12040042
Permit Number 12040042
Review Stop P
Sequence Number 2
Notes
Date Text
2012-06-01 13:15:27FBC 2010 PLUMBING REVIEW #2
  
 ITEM #4 HAS NOT BEEN ADDRESSED. SHEET A-0.0 LISTS
 EDUCATION NUMBER OF OCCUPANTS AT 271 AND ADMINISTRATION
 AT 60. WITH A TOTAL OF 331, FOUR DRINKING FOUNTAINS
 WOULD BE REQUIRED. ALSO NOTE THAT WATER COOLERS OR
 BOTTLED WATER DISPENSERS COULD SUBSTITUTE FOR 50% (2)
 OF THE DRINKING FOUNTAINS.
  
 4. THE TOTAL OCCUPANT LOAD FOR BUILDING APPEARS TO BE
 OVER 300. 4 DRINKING FOUNTAINS WILL BE REQUIRED. 2 ARE
 REQUIRED TO BE ACCESSIBLE.
 NOTE: 410.1 APPROVAL. DRINKING FOUNTAINS...IN OTHER
 OCCUPANCIES, WHERE DRINKING FOUNTAINS ARE REQUIRED,
 WATER COOLERS OR BOTTLED WATER DISPENSERS SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR NOT MORE THAN 50
 PERCENT OF THE REQUIRED DRINKING FOUNTAINS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  