2012-05-29 16:54:15BUILDING PLAN REVIEW
 PERMIT: 12040042
 ADD: 1711 WORTHINGTON BLDG PHASE II BLDG 200
 EDUCATIONAL
 CONT: ONICX LLC
 TEL: (813)964-0666
  
 2010 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 MAY 28/2012
 ACTION: DENIED
  
 1) THE CONTRACTOR IS TO COME IN AND CHANGE THE PERMIT
 APPLICATION UNDER THE HEADING DESCRIPTION OF WORK. THE
 PERMIT APPLICATION AND PLANS NEED TO USE THE SAME
 NOMENCLATURE THE PLANS INDICATE THIS PORTION OF WORK AS
 PHASE II BLDG 200 EDUCATIONAL/ CHANGE IN OCCUPANCY.
  
 2) A-0.0 COVER SHEET & INDEX;
 2A) COMPLIED.
  
 2B) THE PLANS DO NOT PROVIDE DOCUMENTATION IF THIS
 BUILDING IS PROTECTED BY NFPA 13 FIRE SPRIKLER SYSTEM
 OR NOT? INDEX DOES NOT INDICATE ANY FIRE SPINKLER OR
 FIRE PROTECTION PLANS WITHIN THE SET? 106.3.5.1.1(5)
 SCHEMATIC FIRE SPRINKLERS.
  
 2C) THE HEADING OF CODE INFORMATION FBC-B 803.5
 INDICATES, CLASS B FOR EXITS & CORRIDORS/ CLASS C FOR
 ROOMS AND ENCLOSED SPACES THESE RATINGS ARE FOR FIRE
 SPRINKLERED BUILDINGS.
  
 2D) THE COVER SHEET ALSO INDICATES THE USE OF YKK
 YES40F1 WINDOW PRODUCT APPROVALS FL 7606.1 PLEASE NOTE
 THIS REPORT IS FOR NON- MISSILE RATED GLAZING WHICH
 WILL REQUIRE PRODUCT TESTING REPORT FOR STORM PANELS.
  
 THE OTHER ISSUE WITH THE SUBMITTED FL 7606.1 REPORT
 ONLY THE COVER SHEETS WERE UPLOADED, THE ACTUAL
 EVALUATION REPORT WITH PRESSURES WAS NOT INCLUDED NOR
 WAS THE INSTALATION INSTRUCTIONS THAT TIE TO THE
 FLORIDA COVER SHEET.
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR
 REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 2E) THE SECOND PRODUCT APPROVAL THE COVER SHEET LISTED
 IS FOR EXTERIOR OUTSWING YKK DOOR FL 9967.1 NO REPORT
 WAS FOUND UNDER THIS PRODUCT NUMBER.
  
 2F) COMPLIED.
  
 3) SHEET A-1.0:
 3A) PLEASE PROVIDE THE DISTANCE BETWEEN THE TWO
 BUILDINGS AND PROVIDE COMPLIANCE WITH FBC-B TABLE 602
 OR ARE THEY CONSIDERED BUILDINGS ON SAME LOT UNDER
 FBC-B 503.1.2.
  
 3B) PLEASE PROVIDE THE SQ FT PER CLASSROOM AND OCCUPANT
 LOAD FOR EACH ROOM FBC-B TABLE 1004.1.1.
  
 3C) COMPLIED.
  
 3D) SEE FIRE COMMENTS ABOUT FUTURE CLASSROOMS 7 & 8, IF
 TO BE CLASSIFIED AS STORAGE AND NON-SPRINKLERED
 BUILDING SEE TABLE 508.4, 508.2.5.1 FIRE -RESISTANCE
 RATED SEPERATION AND OR 508.2.5.2 NON-FIRE RESISTANCE
 RATED SEPERATION AND CONSTRUCTION REQUIREMENTS.
  
 3E) REPLACEMENT OF EXTERIOR DOORS 116C-120C TO COMPLY
 WITH 2010 FBC-B FIGURE11-404.2.4.3 MANEUVERING
 CLEARENCES AT RECESSED DOORS
  
 3F) CORRIDORS INDICATE A WALL TYPE 2 PLEASE PROVIDE
 COMPLIANCE WITH 2010 FBC-B TABLE 1018.1 1 HOUR FIRE
 RATING FOR NON SPRINKLERED BUILDINGS.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) HIGHLIGHTED REVISION DETAIL 4/M-3.0 IT APPEARS THAT
 THE ALUMINUM STANDS FOR MECHANICAL UNITS ARE DESIGNED
 BY PE FRANK BENNARDO, IF THIS PART OF A PRODUCT
 APPROVAL PLEASE PROVIDE THE COVER SHEET THAT IS
 ASSOCIATED WITH THE PRODUCT APPROVAL, OTHERWISE IS THIS
 A SPECIALTY ENGINEER WORKING UNDER YOUR SUPERVISION?
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  