2012-04-25 09:49:25FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 BUILDING 100
 1. BUILDING 100 DOES NOT INCLUDE THE REQUIRED DRINKING
 FOUNTIAN. PLUMBING 403.1 MINIMUM PLUMBING FIXTURES. PER
 ACCESSIBILITY CODE 2010 - 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 2. THE LAVS IN ROOMS 107 & 108 APPEAR TO BE IN THE 5'
 CLEAR SPACE FOR THE WATER CLOSET. THE TOTAL FOR THE
 RESTROOM WOULD BE 5' + 2'-1" = 7'-1"
 FBC 2010 FLORIDA ACCESSIBILITY CODE 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL. 604.3.2 OVERLAP. THE
 REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE
 PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB
 BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT
 HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE
 AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE
 TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL
 BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
  
 3. A SANITARY RISER DIAGRAM IS REQUIRED PER FBC 106.3.3
 PLUMBING (13)
  
 4. WATER PIPEING IS NOT SHOWN FOR RESTROOMS 107 & 108
  
 BUILDING 200
 1. THE LAVS IN ROOMS 132 & 133 APPEAR TO BE IN THE 5'
 CLEAR SPACE FOR THE WATER CLOSET. THE TOTAL FOR THE
 RESTROOM WOULD BE 5' + 2'-1" = 7'-1"
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL. 604.3.2 OVERLAP. THE
 REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE
 PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB
 BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT
 HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE
 AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE
 TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL
 BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
  
 2. THE SANITARY FOR THE SINGLE USER RESTROOMS IS A WET
 VENT SYSTEM. SINKS SHALL CONNECT DOWNSTREAM OF THE WET
 VENTED FIXTURES.
 909.1 HORIZONTAL WET VENT PERMITTED. ANY COMBINATION OF
 FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE SAME
 FLOOR LEVEL IS PERMITTED TO BE VENTED BY A HORIZONTAL
 WET VENT. THE WET VENT SHALL BE CONSIDERED THE VENT FOR
 THE FIXTURES AND SHALL EXTEND FROM THE CONNECTION OF
 THE DRY VENT ALONG THE DIRECTION OF THE FLOW IN THE
 DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE DRAIN
 CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 3. A SANITARY RISER DIAGRAM IS REQUIRED PER FBC 106.3.3
 PLUMBING (13)
  
 4. THE TOTAL OCCUPANT LOAD FOR BUILDING APPEARS TO BE
 OVER 300. 4 DRINKING FOUNTAINS WILL BE REQUIRED. 2 ARE
 REQUIRED TO BE ACCESSIBLE.
 NOTE: 410.1 APPROVAL. DRINKING FOUNTAINS...IN OTHER
 OCCUPANCIES, WHERE DRINKING FOUNTAINS ARE REQUIRED,
 WATER COOLERS OR BOTTLED WATER DISPENSERS SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR NOT MORE THAN 50
 PERCENT OF THE REQUIRED DRINKING FOUNTAINS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  