Plan Review Notes
Plan Review Notes For Permit 12040042
Permit Number 12040042
Review Stop B
Sequence Number 1
Notes
Date Text
2012-04-10 11:25:15BUILDING PLAN REVIEW
 PERMIT: 12040042
 ADD: 1711 WORTHINGTON BLDG PHASE II BLDG 200
 EDUCATIONAL
 CONT: ONICX LLC
 TEL: (813)964-0666
  
 2010 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE CONTRACTOR IS TO COME IN AND CHANGE THE PERMIT
 APPLICATION UNDER THE HEADING DESCRIPTION OF WORK. THE
 PERMIT APPLICATION AND PLANS NEED TO USE THE SAME
 NOMENCLATURE THE PLANS INDICATE THIS PORTION OF WORK AS
 PHASE II BLDG 200 EDUCATIONAL/ CHANGE IN OCCUPANCY.
  
 2) A-0.0 COVER SHEET & INDEX;
 2A) CODE INFORMATION, THE MINIMUM BUILDING TYPE IS NOT
 PROVIDED ONLY A "B" TYPE 2010 FBC-B WPB ADMINISTRATIVE
 CODE 106.3.5.1.1(3) MINIMUM TYPE OF CONSTRUCTION &
 TABLE 503.
  
 BUILDING 200 PHASE II THE EDUCATIONAL OCCUPANCY
 INDICATES AN AREA OF 11,410 SQ FT, PLEASE PROVIDE THE
 MINIMUM BUILDING TYPE IF AREA INCREASES WERE CONSIDERED
 FOR FRONTAGE OR FIRE SPRINKLERS FBC-B 506.2 AND OR
 506.3.
  
 2B) THE PLANS DO NOT PROVIDE DOCUMENTATION IF THIS
 BUILDING IS PROTECTED BY NFPA 13 FIRE SPRIKLER SYSTEM
 OR NOT? INDEX DOES NOT INDICATE ANY FIRE SPINKLER OR
 FIRE PROTECTION PLANS WITHIN THE SET? 106.3.5.1.1(5)
 SCHEMATIC FIRE SPRINKLERS.
  
 2C) THE HEADING OF CODE INFORMATION FBC-B 803.5
 INDICATES, CLASS B FOR EXITS & CORRIDORS/ CLASS C FOR
 ROOMS AND ENCLOSED SPACES THESE RATINGS ARE FOR FIRE
 SPRINKLERED BUILDINGS.
  
 2D) THE COVER SHEET ALSO INDICATES THE USE OF YKK
 YES40F1 WINDOW PRODUCT APPROVALS FL 7606.1 PLEASE NOTE
 THIS REPORT IS FOR NON- MISSILE RATED GLAZING WHICH
 WILL REQUIRE PRODUCT TESTING REPORT FOR STORM PANELS.
  
 THE OTHER ISSUE WITH THE SUBMITTED FL 7606.1 REPORT
 ONLY THE COVER SHEETS WERE UPLOADED, THE ACTUAL
 EVALUATION REPORT WITH PRESSURES WAS NOT INCLUDED NOR
 WAS THE INSTALATION INSTRUCTIONS THAT TIE TO THE
 FLORIDA COVER SHEET.
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR
 REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 2E) THE SECOND PRODUCT APPROVAL THE COVER SHEET LISTED
 IS FOR EXTERIOR OUTSWING YKK DOOR FL 9967.1 NO REPORT
 WAS FOUND UNDER THIS PRODUCT NUMBER.
  
 2F) THE MINIMUM CORRIDOR WIDTH FOR EDUCTION IS GREATER
 THAN 36" AS INDICATED ON THE COVER SHEET, THE DESIGNER
 IS INDICATING 36 INCHES AS A MINIMUM WIDTH, PLEASE
 REVIEW FBC-B 1018.2(4) FOR EDUCATION SERVING A OCCUPANT
 LOAD OF 100, CORRIDOR WIDTH MINIMUM SHALL BE 72 INCHES.
  
 3) SHEET A-1.0:
 3A) PLEASE PROVIDE THE DISTANCE BETWEEN THE TWO
 BUILDINGS AND PROVIDE COMPLIANCE WITH FBC-B TABLE 602
 OR ARE THEY CONSIDERED BUILDINGS ON SAME LOT UNDER
 FBC-B 503.1.2.
  
 3B) PLEASE PROVIDE THE SQ FT PER CLASSROOM AND OCCUPANT
 LOAD FOR EACH ROOM FBC-B TABLE 1004.1.1.
  
 3C) PLEASE PROVIDE THE DIMENSIONS FOR CORRIDORS THAT
 MAY HAVE 100 OR MORE OCCUPANTS, FBC-B 1018.2(4)
  
 3D) SEE FIRE COMMENTS ABOUT FUTURE CLASSROOMS 7 & 8, IF
 TO BE CLASSIFIED AS STORAGE AND NON-SPRINKLERED
 BUILDING SEE TABLE 508.4, 508.2.5.1 FIRE -RESISTANCE
 RATED SEPERATION AND OR 508.2.5.2 NON-FIRE RESISTANCE
 RATED SEPERATION AND CONSTRUCTION REQUIREMENTS.
  
 3E) REPLACEMENT OF EXTERIOR DOORS 116C-120C TO COMPLY
 WITH 2010 FBC-B FIGURE11-404.2.4.3 MANEUVERING
 CLEARENCES AT RECESSED DOORS
  
 3F) CORRIDORS INDICATE A WALL TYPE 2 PLEASE PROVIDE
 COMPLIANCE WITH 2010 FBC-B TABLE 1018.1 1 HOUR FIRE
 RATING FOR NON SPRINKLERED BUILDINGS, FOR SPRINKLERED
 BUILDINGS FOOTNOTE "C" FORM SMOKE PARTITIONS.
  
 4) SHEET A1.1 DETAIL # 3, INDICATES THE USE OF A
 MICROWAVE PLEASE REVIEW REACH RANGES 11-308.3 SIDE
 APPROACH & 11-309 OPERABLE PARTS.
  
 5) SHEET M-3.0 DETAIL # 11 ROOFTOP EXHAUST FAN NEITHER
 THE ARCHITECTURAL NOR STRUCTURAL SHEETS PROVIDE HOW THE
 ROOF TOP EXHAUST FAN, NOR CURB SHALL
 BE ATTACHED TO THE ROOFTOP. PLANS INDICATE SUPPORT
 ANGLES AS REQUIRED BY THE GENERAL CONTRACTOR!!!
  
 FAN HOUSING TO CURB ANCHORAGE INDICATES TO PLACE
 CADMIUM PLATED SCREWS 12 INCHES ON CENTER, WHAT IS THE
 SCREW DIAMETER AND LENGTH?
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  