2012-05-07 16:57:41 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) THE EXPOSURE CATEGORY SPECIFIED ON SHEET S100 IS |
| INCORRECT. THE STRUCTURE IS LOCATED APPROXIMATELY 656 |
| FEET FROM THE INTRA-COASTAL WATERWAY. THEREFORE, THE |
| SURFACE ROUGHNESS B DOES NOT PREVAIL IN THE UPWIND |
| DIRECTION FOR AT LEAST 1,500 FEET. BASED ON FBC |
| R301.2.1.4.3 THE EXPOSURE CATEGORY FOR THIS STRUCTURE |
| IS C. PLEASE REVISE THE PLANS. |
| |
| 2) PLEASE REVIEW THE DESIGN PRESSURES IN TABLES ON |
| SHEET S100 AND REVISE AS NECESSARY TO COMPLY WITH FBC |
| R301.2.1. |
| |
| 3) ONLY ONE SET OF PRODUCT APPROVALS WERE SUBMITTED. |
| CITY AMENDMENTS 107.1 REQUIRES A MINIMUM OF TWO SETS. |
| PLEASE SUBMIT AN ADDITIONAL SET OF PRODUCT APPROVALS. |
| |
| 4) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| AMENDMENTS 107.3.4.1 |
| |
| 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ROOF |
| TILE AND SPECIFY THE ATTACHMENT METHOD FROM THE PRODUCT |
| APPROVAL THAT WILL BE USED TO INSTALL IT. DCA RULE 9N-3 |
| |
| 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR ALL |
| EXTERIOR DOORS (EXTERIOR LOUVER DOORS, FRENCH DOOR, |
| REFURBISHED DOOR FROM MAIN HOUSE) AS REQUIRED BY DCA |
| RULE 9N-3. THE PRODUCT APPROVAL SUBMITTED FOR THE |
| FRENCH DOOR (CGI 450) IS EXPIRED. IF THE REFURBISHED |
| DOOR DOES NOT HAVE A PRODUCT APPROVAL, THEN IT WILL BE |
| REQUIRED TO BE ENGINEERED IN ACCORDANCE WITH ACCEPTABLE |
| ENGINEERING PRACTICES PER FBC R612.8.3. |
| |
| 7) THE PLANS SPECIFY THAT THE SINGLE HUNG WINDOWS ARE |
| TO BE PGT. PRODUCT APPROVALS WERE SUBMITTED FOR BOTH |
| PGT AND CGI SINGLE HUNG WINDOWS. PLEASE CLARIFY. |
| |
| 8) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE CGI |
| CASEMENT WINDOW IS FOR A SINGLE WINDOW. THE PLANS |
| INDICATE DOUBLE CASEMENT WINDOWS AT THE BEDROOM. BASED |
| ON THE PRODUCT APPROVAL SUBMITTED TWO SINGLE WINDOWS |
| WOULD NEED TO BE JOINED TOGETHER WITH A MULLION WHICH |
| WOULD NOT COMPLY WITH THE REQUIRED MINIMUM OPENING |
| WIDTH OF FBC R310.1.3. PLEASE SHOW COMPLIANCE. |
| |