Plan Review Notes For Permit 12030777 |
Permit Number |
12030777 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-03-30 16:16:03 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST. | | 2010 FLORIDA RESIDENTIAL CODE | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR THE FLAT ROOF ASSEMBLY TO BE | | INSTALLED. NONE SUBMITTED AT THIS TIME. | | | | 2- A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING | | TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | PRESSURES OF SEC. R301.2.1.4.3. | | | | B) TYPICALLY APPROVED ASSEMBLIES ON WOOD DECKS REQUIRE | | NAIL ENHANCING (RAS 117 CALCULATIONS) TO MEET THE | | DESIGN PRESSURES OF SEC. R301.2.1.4.3 FOR PERIMETER AND | | CORNER AREAS. IF THE PRODUCT APPROVAL SUBMITTED | | REQUIRES SIGNED AND SEALED CALCULATIONS, THEN PROVIDE | | SIGNED AND SEALED RAS 117 CALCULATIONS. | | ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO | | TAKE INTO CONSIDERATION THAT THIS BUILDING IS LOCATED | | ON EXPOSURE "C". | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|