Plan Review Notes
Plan Review Notes For Permit 12030654
Permit Number 12030654
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-04-05 12:20:40FIRE DEPARTMENT REVIEW ***DENIED***
 ADDRESS:3330 45TH STREET SUITE A
 PERMIT # 12030654
 CONTRACTOR: CAREY CONSTRUCTION COMPANY
 PHONE: 561 746-1440
  
 1.) ADDRESS ON PLANS DOES NOT MATCH THE ADDRESS ON THE
 PERMIT APPLICATION.
 2.) DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
 3.) ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
 4.) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
 5.) EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL
 BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING
 READING FIRE/SMOKE BARRIER?PROTECT ALL OPENINGS.
 CHARACTERS SHALL BE AT LEAST 4-INCHES IN HEIGHT AND
 HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE SPACED NOT
 MORE THAN 15 FEET ON CENTER. REFERENCE SECTION 8.3.2.4
 OF FLORIDA FIRE PREVENTION CODE ? NFPA 101
 6.) PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY
 SHALL BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
 REFERENCE SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION
 CODE ? NFPA 101
  
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6722
  