Plan Review Notes For Permit 12030652 |
Permit Number |
12030652 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-03-28 11:01:58 | 2007 FBC W/2009 REVISIONS | | | | MECHANICAL REVISION DENIED | | | | 1) THE ENGINEER THAT SIGNED AND SEALED THE REVISION, | | FERNANDO GOMEZ-PINA, IS NOT THE DESIGNER OF RECORD, | | HAROLD TUSSLER, THAT SIGNED AND SEALED THE ORIGINAL | | PLANS. SEE FS 471 AND FAC 61G15-27 FOR SUCCESSOR | | ENGINEER ADOPTING AS HIS OWN THE WORK OF ANOTHER | | ENGINEER. | | | | 2) THE ORIGINAL PLANS INDICATE THAT THE ENTIRE HVAC | | SYSTEM WAS TO BE REPLACED, INCLUDING THE AIR HANDLER | | AND CONDENSING UNIT. THE REVISION INDICATES THAT ONLY | | THE DUCKWORK WAS REPLACED AND NO EQUIPMENT SCHEDULE IS | | PROVIDED ON THE REVISED PLANS. PLEASE CLARIFY. CITY | | AMENDMENTS 106.1.1 | | | | 3) THE 10" TRANSFER DUCT FROM THE MASTER SUITE IS | | UNDERSIZED. FBCR M1602.4 REQUIRES THAT ALL SUPPLY AIR | | INTO THE MASTER SUITE IS TO BE CONSIDERED WHEN SIZING | | THE TRANSFER DUCTS. THEREFORE, THE TRANSFER DUCT SHOULD | | BE 12". PLEASE CORRECT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|