 REVIEW COMMENTS - FIRE DEPARTMENT
 1) DUST EXPLOSION AND FIRE PREVENTION SHALL CONFORM TO
 THE REQUIREMENTS OF CHAPTER 40 OF THE FLORIDA FIRE
 PREVENTION CODE (NFPA 1 FLORIDA EDITION).
 2) INDICATE IF ANY HOODS OR ENCLOSURES WILL BE USED
 WITH THE EQUIPMENT (SAWS, SANDERS) TO INCREASE THE
 EFFECIENCY OF DUST COLLECTION SYSTEM.
 3) INDICATE HOW THE DUCTWORK CONVEYING THE COMBUSTIBLE
 DUST WILL BE PROTECTED AGAINST FIRE OR DEFLAGRATION
 HAZARDS PER NFPA 664.
 4) DUCTWORK, WOODWORKING EQUIPMENT, AND DUST COLLECTORS
 NEED TO BE BONDED AND GROUNDED TO PREVENT STATIC
 ELECTRICITY AS AN IGNITION SOURCE
 5) DETAIL "A" NOT PROVIDED ON MECHANICAL SHEET.
 6) THE SUBMITTED DOCUMENTS REFERENCE AN EXCEPTION TO
 THE SPRINKLER REQUIREMENT FOUND IN NFPA 664 SECTION
 8.2.2.5.2; HOWEVER, THE IRD DUST COLLECTOR (MODEL
 460-IRD-20) INDICATES A FLOW RATE GREATER THAN 5000
 CFM.
 7) IN ADDITION TO EXIT SIGNS, EMERGENCY LIGHTING SHALL
 BE PROVIDED. RECOMMEND COMBINATION EXIT SIGN/EMERGENCY
 LIGHT FIXTURES.
  
 NOTES:
 1) WOODWORKING FACILITIES LARGER THAN 2,500 SQ.FT. ARE
 REQUIRED TO BE PROTECTED BY AN AUTOMATIC SPRINKLER
 SYSTEM.
 2) THIS ADDRESS DOES NOT HAVE A CURRENT BUSINESS TAX
 RECEIPT FROM THE CITY OF WEST PALM BEACH.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  