2012-04-09 11:57:18****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. ENGINEERING TO BE PREPARED BY A DESIGN PROFESSIONAL,
 FS471. TITLE BLOCK TO INCLUDE ALL LEGALLY REQUIRED
 INFORMATION, FAC61G15-23.
  
 2. INCLUDE RISK CATEGORY IN WIND DESIGN CRITERIA SO
 WIND SPEED CAN BE VERIFIED, FBC FIGURE 1609A.
  
 3. SPECIFY FASTENERS AND FASTENING PATTERN FOR ALL
 SIGNS TO SHOW HOW PROPOSED SIGN WILL RESIST WIND LOADS
 FBC 1609.
  
  
  
  