2012-06-19 17:05:29 | RESIDENTIAL (R3) RENOVATION/ALTERATION SECOND BUILDING |
| REVIEW COMMENTS. |
| 2010 FBC. |
| |
| 1- ARCHITECT TO COORDINATE PLANS WITH THE REVISED |
| ENERGY CALCULATIONS. NEED TO MEET THE MINIMUM |
| REQUIREMENTS OF TABLE 402.1.1 OF 2010 FBC-ENERGY |
| CONSERVATION. SEE COMMENTS ON ITEM 2 BELOW AND |
| COORDINATE ACCORDINGLY. |
| |
| 2- ENERGY CALCULATIONS SUBMITTED (SEC. 107.2.1 CITY |
| AMENDMENTS TO FBC): |
| |
| A) NEED TO MEET ALL THE MINIMUM REQUIREMENTS OF TABLE |
| 402.1.1. REVISE THE WINDOWS AND DOORS FENESTRATION, |
| CEILING INSULATION, WALL INSULATION, ETC. AND |
| COORDINATE WITH REVISED ARCHITECT'S PLANS. SEE ITEM #1 |
| ABOVE. |
| |
| B) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| FORM. SPECIFY BUILDER NAME. COORDINATE WITH OWNER. AND, |
| REVISE THE JURISDICTION NO. THIS IS JURISDICTION 604700 |
| NOT 661200. |
| |
| C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| |
| D) REVISE DOOR TYPE ON SHEET 3 OF 5. PRODUCT APPROVAL |
| SUBMITTED FOR THE DOORS SHOW DOORS WITH MORE THAN 1/3 |
| OF GLAZING ON THE DOOR. REVISE AS REQUIRED BY SEC. |
| 405.5.3 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| E) TAKING CEILING FAN CREDIT ON ITEM #15. ARCHITECT'S |
| PLANS DON'T SHOW CEILING FAN. COORDINATE/REVISE AS |
| REQUIRED. |
| |
| F) THERE IS NOT KITCHEN ON THIS BUILDING. REVISE |
| INFORMATION ON SHEET 2 OF 5. |
| |
| G) REVISE AREAS SHOWN ON THE WINDOWS ON SHEET 3 OF 5 TO |
| MATCH FLOOR PLANS AND ELEVATIONS SHOWN BY THE |
| ARCHITECT. |
| |
| H) SHEET 4 OF 5 SAYS NO MECHANICAL VENTILATION. |
| COORDINATE WITH ARCHITECT'S PLANS AND REVISE AS |
| REQUIRED. |
| |
| 3- ARCHITECT TO REVISE ICYNENE INSULATION |
| SPECIFICATIONS WALLS SECTIONS. ICYNENE IS AN OPEN CELL |
| FOAM NOT CLOSED CELL. ALSO, COORDINATE WITH THE ENERGY |
| CALCULATIONS AND THICKNESS REQUIRED TO MEET THE MINIMUM |
| INSULATION REQUIRED BY TABLE 402.1.1. |
| |
| ***NOTE: PLEASE PROVIDE RESPONSE IN WRITING TO EXPEDITE |
| THE REVIEW PROCESS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |