2012-06-19 17:05:29RESIDENTIAL (R3) RENOVATION/ALTERATION SECOND BUILDING
 REVIEW COMMENTS.
 2010 FBC.
  
 1- ARCHITECT TO COORDINATE PLANS WITH THE REVISED
 ENERGY CALCULATIONS. NEED TO MEET THE MINIMUM
 REQUIREMENTS OF TABLE 402.1.1 OF 2010 FBC-ENERGY
 CONSERVATION. SEE COMMENTS ON ITEM 2 BELOW AND
 COORDINATE ACCORDINGLY.
  
 2- ENERGY CALCULATIONS SUBMITTED (SEC. 107.2.1 CITY
 AMENDMENTS TO FBC):
  
 A) NEED TO MEET ALL THE MINIMUM REQUIREMENTS OF TABLE
 402.1.1. REVISE THE WINDOWS AND DOORS FENESTRATION,
 CEILING INSULATION, WALL INSULATION, ETC. AND
 COORDINATE WITH REVISED ARCHITECT'S PLANS. SEE ITEM #1
 ABOVE.
  
 B) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. SPECIFY BUILDER NAME. COORDINATE WITH OWNER. AND,
 REVISE THE JURISDICTION NO. THIS IS JURISDICTION 604700
 NOT 661200.
  
 C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 D) REVISE DOOR TYPE ON SHEET 3 OF 5. PRODUCT APPROVAL
 SUBMITTED FOR THE DOORS SHOW DOORS WITH MORE THAN 1/3
 OF GLAZING ON THE DOOR. REVISE AS REQUIRED BY SEC.
 405.5.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 E) TAKING CEILING FAN CREDIT ON ITEM #15. ARCHITECT'S
 PLANS DON'T SHOW CEILING FAN. COORDINATE/REVISE AS
 REQUIRED.
  
 F) THERE IS NOT KITCHEN ON THIS BUILDING. REVISE
 INFORMATION ON SHEET 2 OF 5.
  
 G) REVISE AREAS SHOWN ON THE WINDOWS ON SHEET 3 OF 5 TO
 MATCH FLOOR PLANS AND ELEVATIONS SHOWN BY THE
 ARCHITECT.
  
 H) SHEET 4 OF 5 SAYS NO MECHANICAL VENTILATION.
 COORDINATE WITH ARCHITECT'S PLANS AND REVISE AS
 REQUIRED.
  
 3- ARCHITECT TO REVISE ICYNENE INSULATION
 SPECIFICATIONS WALLS SECTIONS. ICYNENE IS AN OPEN CELL
 FOAM NOT CLOSED CELL. ALSO, COORDINATE WITH THE ENERGY
 CALCULATIONS AND THICKNESS REQUIRED TO MEET THE MINIMUM
 INSULATION REQUIRED BY TABLE 402.1.1.
  
 ***NOTE: PLEASE PROVIDE RESPONSE IN WRITING TO EXPEDITE
 THE REVIEW PROCESS.
  