Plan Review Notes
Plan Review Notes For Permit 12030498
Permit Number 12030498
Review Stop B
Sequence Number 1
Notes
Date Text
2012-04-20 13:14:50RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS.
 2010 FLORIDA RESIDENTIAL CODE.
  
 1- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) METAL ROOFING. FLORIDA PRODUCT APPROVAL FL12114-
 SUBMITTED IS FOR 2007 CODE VERSION. NEED TO PROVIDE
 PRODUCT APPROVAL FOR 2010 CODE VERSION.
  
 B) DOUBLE HUNG WINDOW. FLORIDA PRODUCT APPROVAL
 FL4765-R3 SUBMITTED IS FOR 2007 CODE VERSION. NEED 2010
 CODE VERSION.
  
 C) EXTERIOR INSWING DOOR AS SHOWN ON PLANS FOR NEW
 BATHROOM.
  
 D) EXTERIOR OUTSWING DOOR. FLORIDA PRODUCT APPROVAL
 FL4809-R6 SUBMITTED IS FOR 2007 CODE VERSION. NEED 2010
 CODE VERSION.
 ***NOTE: NOA 11-1026.04 SUBMITTED IS OK. YOU MAY SUBMIT
 NOA ALONE.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 4- ENERGY CALCULATIONS SUBMITTED:
 A) CODE IN EFFECT IS THE 2010 FBC. NEED TO USE FORM
 405. REVISE AS REQUIRED. SEE SEC. 405.4.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 B) REVISE ITEM #8(A). BUILDING IS NOT ON SLAB ON GRADE.
 SEE PLANS AND REVISE AS REQUIRED.
  
 C) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. SPECIFY BUILDER NAME. COORDINATE WITH OWNER. AND,
 REVISE THE JURISDICTION NO. THIS IS JURISDICTION 604700
 NOT 661200.
  
 D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 E) REVISE DOOR TYPE ON SHEET 3 OF 5. PRODUCT APPROVAL
 SUBMITTED FOR THE DOORS SHOW DOORS WITH MORE THAN 1/3
 OF GLAZING ON THE DOOR. REVISE AS REQUIRED BY SEC.
 405.5.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 F) THERE IS NOT GARAGE. REVISE INFORMATION ON SHEET 3
 OF 5 SUBMITTED.
  
 5- SPECIFY LANDING ON EXTERIOR SIDE OF DOOR AT THE
 BATHROOM AS REQUIRED BY SEC. R311.3.
  
 6- PROVIDE COMPLETE MANUFACTURER SPECIFICATIONS FOR
 TYPE OF FOAM INSULATION SPECIFIED ON PLANS TO VERIFY
 COMPLIANCE WITH SEC. R316. . ARCHITECT TO REVIEW SPECS
 PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 7- DRAWING S-1 IS MISSING THE ENGINEER'S SEAL AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 8- SHEET C-1.0:
 A) REVISE ALL THE GENERAL NOTES THAT REFERENCE THE 2007
 FBC. CURRENT CODE IS THE 2010 FLORIDA RESIDENTIAL CODE
 AND 2010 EXISTING BUILDING CODE.
  
 B) THIS IS NOT ALTERATION TYPE 2. SCOPE OF WORK IS MORE
 THAN 50%. THIS IS ALT. TYPE 3. SEE CHAPTER 4 OF 2010
 EXISTING BUILDING CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712