 209 S. OLIVE AVE.
 R-3 WITH STORAGE RESIDENTIAL UNIT
  
 VERIFY THAT ALL NEW AND EXISTING EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING
 RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND
 CURRENT THAT IS AVAILABLE. NEC 110.9
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
 VERIFY THE ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND
 GROUPED IN ONE LOCATION. THE SITE PLANS SUGGEST THIS
 BUILDING MAY BE ALREADY SERVED FROM ANOTHER LOCATION.
 NEC 230.2, 230.71
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 ALL NEW RECEPTACLES SHALL BE TAMPER RESISTANT. 2008 NEC
 406.11
 GFCI PROTECTION REQUIRED FOR RECEPTACLES IN THE GARAGE.
 NEC 210.8
  