2012-04-25 16:04:48 | RESIDENTIAL (R3) RENOVATION BUILDING REVIEW COMMENTS. |
| 2007 FBC-EXISTING BUILDING. FLORIDA RESIDENTIAL CODE |
| WITH 2009 REVISIONS. |
| |
| 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| N1100.3. COORDINATE INFORMATION WITH ITEM #2 BELOW. |
| PLEASE MAKE SURE ALL THE INFORMATION IS COMPLETED IN |
| THE FORM AND OWNER/AGENT SIGNS AND DATES FORM ALSO. |
| |
| 2- SEC R806.1 REQUIRES ROOF VENTILATION. OTHERWISE |
| UNVENTED ATTIC NEEDS TO BE DESIGNED BY AN ARCHITECT OR |
| ENGINEER. ENGINEER OF RECORD TO PROVIDE COMPLETE |
| DETAIL/S SPECS ON PLANS AS REQUIRED BY SEC. R806.1 AND |
| R806.4. |
| |
| 3- PROVIDE CURRENT ESR REPORT FOR THE ICYNENE |
| INSULATION TO BE INSTALLED. REPORT SUBMITTED IS |
| EXPIRED. VISIT THE ICC WEBSITE AND DOWNLOAD CURRENT |
| REPORT. |
| |
| 4- FLAT ROOF PRODUCT APPROVAL: PROVIDE SIGNED AND |
| SEALED RAS 117 CALCULATIONS (2 COPIES) AS REQUIRED BY |
| GENERAL LIMITATION #7 ON LAST PAGE OF NOA 09-0224.01 |
| SUBMITTED. NEED CALCULATIONS TO MEET THE DESIGN |
| PRESSURES REQUIRED BY SEC. R301.2.1.4.3. |
| |
| 5- SHEET A-1: |
| A) SPECIFY EMERGENCY EGRESS FROM MASTER BEDROOM AS |
| REQUIRED BY SEC. R310. SPECIFY WINDOW WIDTH, WINDOW |
| HEIGHT AND TOTAL CLEAR OPEN AREA. |
| |
| B) IDENTIFY EGRESS WINDOWS ON FIRST FLOOR BEDROOMS |
| WINDOWS TO VERIFY COMPLIANCE WITH SEC. R310. |
| |
| C) DESIGN PARAMETERS. REVISE ALTERATION TYPE SPECIFIED. |
| THIS IS NOT ALTERATION TYPE II. SEE CHAPTER 4 OF 2007 |
| FBC-EXISTING BUILDING AND REVISE CLASSIFICATION OF WORK |
| AS REQUIRED. |
| |
| 6- SPECIFY SAFETY GLASS FOR WINDOW IN NOOK AREA, MASTER |
| BATHROOM WINDOWS BY THE TUB AREA AS REQUIRED BY SEC. |
| R308.4 |
| |
| 7- SHEET S-1: SPECIFY OVERFLOW SCUPPERS AS REQUIRED BY |
| SEC. R903.4.1. |
| |
| 8- SHEET S-2: REVISE DETAIL 1/S-2. RISER AND TREAD |
| RATIO DOESN'T COMPLY WITH SEC. R311.5.3.2. |
| |
| 9- DRAWINGS S-2 AND S-3 ARE MISSING ENGINEER'S SEAL AS |
| REQUIRED BY CHAPTER 471 FLORIDA STATUTE. ONLY ONE SET |
| OF PLANS HAS THE SEAL. NEED SEAL ON THE OTHER SET. |
| |
| 10- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR ALL THE |
| SIMPSON STRUCTURAL COMPONENTS SPECIFIED ON PLANS AND |
| DETAILS AS REQUIRED BY DCA RULE 9N-3. |
| |
| 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| |
| 12- PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR NEW |
| TRELLIS SHOWN ON SHEET SP-1. NO INFORMATION WAS |
| SUBMITTED. |
| |