2012-04-25 16:04:48RESIDENTIAL (R3) RENOVATION BUILDING REVIEW COMMENTS.
 2007 FBC-EXISTING BUILDING. FLORIDA RESIDENTIAL CODE
 WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3. COORDINATE INFORMATION WITH ITEM #2 BELOW.
 PLEASE MAKE SURE ALL THE INFORMATION IS COMPLETED IN
 THE FORM AND OWNER/AGENT SIGNS AND DATES FORM ALSO.
  
 2- SEC R806.1 REQUIRES ROOF VENTILATION. OTHERWISE
 UNVENTED ATTIC NEEDS TO BE DESIGNED BY AN ARCHITECT OR
 ENGINEER. ENGINEER OF RECORD TO PROVIDE COMPLETE
 DETAIL/S SPECS ON PLANS AS REQUIRED BY SEC. R806.1 AND
 R806.4.
  
 3- PROVIDE CURRENT ESR REPORT FOR THE ICYNENE
 INSULATION TO BE INSTALLED. REPORT SUBMITTED IS
 EXPIRED. VISIT THE ICC WEBSITE AND DOWNLOAD CURRENT
 REPORT.
  
 4- FLAT ROOF PRODUCT APPROVAL: PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS (2 COPIES) AS REQUIRED BY
 GENERAL LIMITATION #7 ON LAST PAGE OF NOA 09-0224.01
 SUBMITTED. NEED CALCULATIONS TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.2.1.4.3.
  
 5- SHEET A-1:
 A) SPECIFY EMERGENCY EGRESS FROM MASTER BEDROOM AS
 REQUIRED BY SEC. R310. SPECIFY WINDOW WIDTH, WINDOW
 HEIGHT AND TOTAL CLEAR OPEN AREA.
  
 B) IDENTIFY EGRESS WINDOWS ON FIRST FLOOR BEDROOMS
 WINDOWS TO VERIFY COMPLIANCE WITH SEC. R310.
  
 C) DESIGN PARAMETERS. REVISE ALTERATION TYPE SPECIFIED.
 THIS IS NOT ALTERATION TYPE II. SEE CHAPTER 4 OF 2007
 FBC-EXISTING BUILDING AND REVISE CLASSIFICATION OF WORK
 AS REQUIRED.
  
 6- SPECIFY SAFETY GLASS FOR WINDOW IN NOOK AREA, MASTER
 BATHROOM WINDOWS BY THE TUB AREA AS REQUIRED BY SEC.
 R308.4
  
 7- SHEET S-1: SPECIFY OVERFLOW SCUPPERS AS REQUIRED BY
 SEC. R903.4.1.
  
 8- SHEET S-2: REVISE DETAIL 1/S-2. RISER AND TREAD
 RATIO DOESN'T COMPLY WITH SEC. R311.5.3.2.
  
 9- DRAWINGS S-2 AND S-3 ARE MISSING ENGINEER'S SEAL AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE. ONLY ONE SET
 OF PLANS HAS THE SEAL. NEED SEAL ON THE OTHER SET.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR ALL THE
 SIMPSON STRUCTURAL COMPONENTS SPECIFIED ON PLANS AND
 DETAILS AS REQUIRED BY DCA RULE 9N-3.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 12- PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR NEW
 TRELLIS SHOWN ON SHEET SP-1. NO INFORMATION WAS
 SUBMITTED.
  