Plan Review Notes For Permit 12030350 |
Permit Number |
12030350 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-05-16 08:28:56 | 2010 FBC | | | | DENIED BY MECHANICAL | | | | 1) THE ENERGY CALCULATIONS THAT WERE SUBMITTED ARE ON | | THE FORMS FOR THE 2010 FBC AND THIS PROJECT IS UNDER | | THE 2007 FBC. PLEASE SUBMIT THE CORRECT FORMS. 2007 FBC | | ENERGY GLITCH AMENDMENTS N1100.1 | | | | 2) THE HVAC EQUIPMENT CAN NOT BE SIZED USING WORST- | | CASE SIZING, THE ACTUAL BUILDING ORIENTATION MUST BE | | USED. SEE 2007 FBC ENERGY GLITCH AMENDMENTS N1107.AB.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|