2012-05-16 11:19:25 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY BUILDING | | | | 1) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR | | THE PROJECT. CITY AMENDMENTS 106.3.3 | | | | 2) THE ENERGY CALCULATION FORM THAT WAS SUBMITTED IS | | THE ONE FOR THE 2010 FBC. PLEASE SUBMIT THE CORRECT | | FORMS FOR THE 2007 FBC. 2007 FBC ENERGY GLITCH | | AMENDMENTS N1100 | | | | 3) THE ENERGY CALCULATIONS THAT WERE SUBMITTED ARE | | WORST- CASE. THIS IS NOT PERMITTED FOR SIZING THE | | HEATING AND COOLING EQUIPMENT. PLEASE CORRECT. 2007 FBC | | ENERGY GLITCH | | AMENDMENTS N1107.AB.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|