2012-05-16 11:19:252007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 106.3.3
  
 2) THE ENERGY CALCULATION FORM THAT WAS SUBMITTED IS
 THE ONE FOR THE 2010 FBC. PLEASE SUBMIT THE CORRECT
 FORMS FOR THE 2007 FBC. 2007 FBC ENERGY GLITCH
 AMENDMENTS N1100
  
 3) THE ENERGY CALCULATIONS THAT WERE SUBMITTED ARE
 WORST- CASE. THIS IS NOT PERMITTED FOR SIZING THE
 HEATING AND COOLING EQUIPMENT. PLEASE CORRECT. 2007 FBC
 ENERGY GLITCH
 AMENDMENTS N1107.AB.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]