Plan Review Notes
Plan Review Notes For Permit 12030350
Permit Number 12030350
Review Stop M
Sequence Number 1
Notes
Date Text
2012-04-03 10:27:352007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE ENERGY CALCULATION FORMS ARE REQUIRED BY BE
 SIGNED BY THE OWNER/AGENT. 2007 FBC ENERGY GLITCH
 AMENDMENTS N1100.2.2
  
 2) SUBMIT TWO SETS OF MECHANICAL PLANS WITH DUCT LAYOUT
 AND EQUIPMENT SCHEDULE. SPECIFY THE DUCT AND GRILL
 SIZES, SPECIFY CFMS AT EACH DROP AND SHOW LOCATIONS OF
 ALL EQUIPMENT. CITY AMENDMENTS 106.3.5.4
  
 3) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED
 RETURN AIR.
  
 4) NOTE: THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE
 WHICH REQUIRES ALL MECHANICAL EQUIPMENT TO BE LOCATED
 ABOVE 7.5 FEET BFE. AN ELEVATION CERTIFICATE WILL BE
 REQUIRED AT FINAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]