2012-04-04 13:42:00 | 2007 FBC W/2009 REVISIONS |
| |
| DENIED BY BUILDING |
| |
| 1) THE PROPOSED STRUCTURE IS LOCATED IN AN A5 FLOOD |
| ZONE. THE MINIMUM FINISHED FLOOR ELEVATION IS 7.5 FEET |
| B.F.E. PER CITY FLOOD ORDINANCE. PLEASE SPECIFY THE |
| PROPOSED FLOOR ELEVATIONS ON THE PLANS. ELEVATION |
| CERTIFICATES WILL BE REQUIRED. |
| |
| 2) ON SHEETS A3 AND A4 THE WRONG EXPOSURE CATEGORY IS |
| SPECIFIED. THE STRUCTURE IS LOCATED IN EXPOSURE |
| CATEGORY C PER FBC R301.2.1.4.3. PLEASE CORRECT. |
| |
| 3) THE COMPONENT AND CLADDING PRESSURES WILL NEED TO BE |
| INCREASED TO CORRESPOND WITH EXPOSURE C. FBC R301.2.1 |
| |
| 4) SUBMIT TWO COPIES OF A SITE DRAINAGE PLAN COMPLYING |
| WITH FBC R401.3. |
| |
| 5) THE ENERGY CALCULATION FORM SPECIFIES A VENTED ATTIC |
| AND THE WALL SECTIONS ON SHEET D1 APPEAR TO SHOW AN |
| UNVENTED ATTIC. PLEASE CLARIFY. IF ATTIC IS VENTED, |
| SPECIFY THE ATTIC VENTILATION ON THE PLANS SHOWING |
| COMPLIANCE WITH FBC R806. IF IT IS UNVENTED, SUBMIT TWO |
| COPIES OF THE MANUFACTURER'S PRODUCT EVALUATIONS FOR |
| THE SPRAY FOAM INSULATION. |
| |
| 6) FBC R613.6.1.1 REQUIRES WINDOW AND DOOR BUCKS TO BE |
| THE FULL WIDTH OF THE FRAMES. PLEASE REVISE BUCK |
| DETAILS. |
| |
| 7) A 30" ROOF OVERHANG IS SPECIFIED ON THE |
| ARCHITECTURAL DRAWINGS AND A 12" ONE IS SHOWN ON THE |
| STRUCTURAL PLANS. PLEASE COORDINATE PROJECTION OF THE |
| OVERHANG. CITY AMENDMENTS 106.1.1 |
| |
| 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE 16' |
| WIDE GARAGE DOOR AS REQUIRED BY DCA RULE 9N-3. THE ONE |
| SUBMITTED HAS A MAXIMUM WIDTH LIMITATION OF 9 FEET. |
| |
| 9) PLEASE REVIEW THAT DESIGN PRESSURES FOR THE PRODUCTS |
| THAT WERE SUBMITTED TO VERIFY THAT THEY WILL MEET THE |
| INCREASED DESIGN PRESSURE REQUIREMENTS FOR EXPOSURE |
| CATEGORY C. |
| |
| 10) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| THE PROJECT. CITY AMENDMENTS 106.3.3 |
| |
| 11) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY |
| CALCULATION FORMS. 2007 FBC ENERGY GLITCH AMENDMENTS |
| N1100.2.2 |
| |
| 12) THE ENERGY CALCULATION FORM INCORRECTLY SPECIFIES |
| 3525 SQUARE FEET UNDER ATTIC. A PORTION OF THIS |
| STRUCTURE IS TWO STORIES. THERE IS A TOTAL OF 3525 SQFT |
| OF CONDITIONED AREA AND THE SECOND FLOOR IS 1244 SQFT. |
| PLEASE CORRECT THE FORM. 2007 FBC ENERGY GLITCH |
| AMENDMENTS N1100 |
| |
| 13) THE ENERGY CALCULATIONS THAT WERE SUBMITTED ARE |
| WORSE CASE. THIS IS NOT PERMITTED FOR SIZING THE |
| HEATING AND COOLING EQUIPMENT. PLEASE CORRECT. 2007 FBC |
| ENERGY GLITCH |
| AMENDMENTS N1107.AB.1 |
| |
| 14) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW THE |
| REVIEW COMMENTS HAVE BEEN ADDRESSED. |
| |