2012-06-06 20:44:06 | PLANNING: ***** FAILED *****] |
| |
| |
| 1, RESPOND TO COMMENTS IN WRITING WHEN RESUBMITING |
| DOCUMENTS. |
| |
| 2. THE SCOPE OF WORK DENOTES ALL INTERIOR WORK AND |
| RENOVATIONS, HOWEVER, SHEET E1, PLAN NOTES CALLS OUT |
| FOR A PROPOSED ASC GENERATOR. THERE ARE NO CIVIL |
| DRAWINGS THAT SHOW THIS GENERATOR OR ENCLOSURE. IS |
| THERE A NEW GENERATOR PROPOSED? |
| |
| IF SO, PROVIDE THE FOLLOWING INFORMATION: |
| |
| A. INDICATE SETBACK DIMENSIONS FROM PROPOSED GENERATOR |
| EQUIPMENT TO ALL PROPERTY LINES. PURSUANT TO SECTION |
| 94-305(B)(4) OF THE ZLDR: MECHANICAL EQUIPMENT MAY NOT |
| PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. |
| |
| RESUBMITTAL: DIMENSIONS WERE NOT PROVIDED ON SITE PLAN |
| SP-1 OR LP-1. |
| |
| B. PROVIDE ELEVATIONS AND A FLOOR PLAN OF SCREENING AND |
| LANDSCAPING DETAIL. INCLUDE WALL HEIGHT, ETC. SCREENING |
| ENCLOSURE AND LANDSCAPING SHALL MEET SECTION 94-444 OF |
| THE ZONING AND LAND DEVELOPMENT REGULATIONS. SCREENING |
| WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES |
| PLANTED AT TWO-FOOT INTERVALS. OR PROVIDE INFORMATION |
| OF EXISTING ENCLOSURE THAT MEETS THE REQUIREMENTS |
| ABOVE. |
| |
| RESUBMITTAL: ELEVATIONS WERE NOT PROVIDED. PROVIDE A |
| CROSS SECTION OF THE PROPOSED ENCLOSURE, GENERATOR |
| (INCLUDING THE MOUNTING AND TANK), THE ENTIRE GENERATOR |
| EQUIPMENT NEEDS TO BE SCREENED FROM VIEW. PROVIDE TOTAL |
| HEIGHT DIMENSIONS OF FENCE ENCLOSURE AND GENERATOR. |
| |
| |
| |
| IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. |
| |