Plan Review Notes
Plan Review Notes For Permit 12030309
Permit Number 12030309
Review Stop Z
Sequence Number 2
Notes
Date Text
2012-06-06 20:44:06PLANNING: ***** FAILED *****]
  
  
 1, RESPOND TO COMMENTS IN WRITING WHEN RESUBMITING
 DOCUMENTS.
  
 2. THE SCOPE OF WORK DENOTES ALL INTERIOR WORK AND
 RENOVATIONS, HOWEVER, SHEET E1, PLAN NOTES CALLS OUT
 FOR A PROPOSED ASC GENERATOR. THERE ARE NO CIVIL
 DRAWINGS THAT SHOW THIS GENERATOR OR ENCLOSURE. IS
 THERE A NEW GENERATOR PROPOSED?
  
 IF SO, PROVIDE THE FOLLOWING INFORMATION:
  
 A. INDICATE SETBACK DIMENSIONS FROM PROPOSED GENERATOR
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT TO SECTION
 94-305(B)(4) OF THE ZLDR: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 RESUBMITTAL: DIMENSIONS WERE NOT PROVIDED ON SITE PLAN
 SP-1 OR LP-1.
  
 B. PROVIDE ELEVATIONS AND A FLOOR PLAN OF SCREENING AND
 LANDSCAPING DETAIL. INCLUDE WALL HEIGHT, ETC. SCREENING
 ENCLOSURE AND LANDSCAPING SHALL MEET SECTION 94-444 OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS. SCREENING
 WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS. OR PROVIDE INFORMATION
 OF EXISTING ENCLOSURE THAT MEETS THE REQUIREMENTS
 ABOVE.
  
 RESUBMITTAL: ELEVATIONS WERE NOT PROVIDED. PROVIDE A
 CROSS SECTION OF THE PROPOSED ENCLOSURE, GENERATOR
 (INCLUDING THE MOUNTING AND TANK), THE ENTIRE GENERATOR
 EQUIPMENT NEEDS TO BE SCREENED FROM VIEW. PROVIDE TOTAL
 HEIGHT DIMENSIONS OF FENCE ENCLOSURE AND GENERATOR.
  
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: (561) 822-1443
 EMAIL: [email protected]
  