 RENOVATIONS TO SURGERY CENTER
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 EQUIPMENT WHICH INCLUDES THE SPECIFIC WORDING REGARDING
 THE SIZE AND TYPE OF HAZARDS. 2008 NEC 110.22, 110.16
 INDICATE ON THE PLANS THE REQUIREMENT FOR A SIGN WHICH
 INDICATES THE TYPE AND LOCATION OF THE ON SITE
 EMERGENCY POWER SOURCE. NEC 700.8
 VERIFY THE GENERATOR IS A LEVEL 1, TYPE 10, CLASS 8.
 2010 FBC 421.3.13
 PROVIDE A WIRING METHOD TO CONNECT A PORTABLE OR
 TEMPORARY ALTERNATE SOURCE OF POWER AS REQUIRED
 WHENEVER THE EMERGENCY GENERATOR IS OUT OF SERVICE FOR
 MAJOR MAINTENANCE OR REPAIR. NEC 700.5(B)
  
  