2012-05-31 10:50:18 | THURSDAY, MAY 31, 2012 | | 1203309 | | 2047 PALM BEACH LAKES BLVD. | | RENOVATIONS TO SURGERY CENTER | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL | | EQUIPMENT WHICH INCLUDES THE SPECIFIC WORDING REGARDING | | THE SIZE AND TYPE OF HAZARDS. 2008 NEC 110.22, 110.16 | | INDICATE ON THE PLANS THE REQUIREMENT FOR A SIGN WHICH | | INDICATES THE TYPE AND LOCATION OF THE ON SITE | | EMERGENCY POWER SOURCE. NEC 700.8 | | VERIFY THE GENERATOR IS A LEVEL 1, TYPE 10, CLASS 8. | | 2010 FBC 421.3.13 | | PROVIDE A WIRING METHOD TO CONNECT A PORTABLE OR | | TEMPORARY ALTERNATE SOURCE OF POWER AS REQUIRED | | WHENEVER THE EMERGENCY GENERATOR IS OUT OF SERVICE FOR | | MAJOR MAINTENANCE OR REPAIR. NEC 700.5(B) | | | | | | ROBERT LECKY, CBO | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|