2012-06-01 11:26:34BUILDING PLAN REVIEW
 PERMIT: 12030309
 ADD: 2047 PALM BEACH LAKES
 CONT: LEIGHTON MCGINN
 TEL: (561)722-9697
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A6 DETAIL #1 OVERFLOW SCUPPER LOCATION ALLOWS
 FOR 6" OF PONDING WHEN THE MAIN SCUPPERS ARE BLOCKED,
 SECTION 1503.4.3 ALLOWS FOR 2-4 INCHES OF PONDING
 MAXIMUM. REVISION IS REQUIRED BY THE ROOF SHEATHING
 INSPECTION.
  
 1503.4.3 OVERFLOW SCUPPERS. WHEN OTHER MEANS OF
 DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW
 SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS
 THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM)
 ABOVE THE FINISHED ROOF COVERING AND SHALL BE LOCATED
 AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR
 DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW
 SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, PLUMBING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
 CONTRACTOR TO COLAGATE PLANS BEFORE ISSUANCE.