2012-03-26 15:27:121203309
 2047 PALM BEACH LAKES BLVD.
 RENOVATIONS TO SURGERY CENTER
  
  
 PROVIDE PANEL SCHEDULES AND A SUMMARY LOAD CALCULATION.
 LOCATE THE GENERATOR ON THE SITE PLAN. NEC 215.5
 SPECIFY ON THE PLANS THE REQUIRED WIRING METHODS
 SUITABLE FOR HEALTH CARE FACILITIES. INCLUDE NUMBER OF
 RECEPTACLES AND TYPES LOCATED AT EACH PATIENT CARE
 AREA. SPECIFY THE BRANCHS IE. LS, CR OR EQ. INDICATE
 THE LIFE SAFETY BRANCH AND CRITICAL BRANCH OF THE
 EMERGENCY SYSTEM ARE TO BE INDEPENDENT OF ALL OTHER
 WIRING. NEC 517
 PROVIDE A DETAIL VERIFYING THE REQUIRED WORKING
 CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN
 PROVIDED FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS.
 NEC 110.26, 240.24,
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES.
 SPACE CONTROL FBC 13-415 ABC.1.2.; ADDITIONAL CONTROLS
 13-415.ABC.1.3
  
 PLANS ARE NOT CLEAR AS TO THE SCOPE OF THE NEW ELECTRIC
 WORK. A TYPE I ESSENTIAL ELECTRIC SYSTEM REQUIRES A
 REMOTE GENERATOR ANNUNCIATOR. THE EMERGENCY AND NORMAL
 ELECTRIC SERVICE MAINS REQUIRE SEPARATE ROOMS. SHEET E5
 APPEARS INCOMPLETE.
  
 NOTE:
 SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 ALARM SYSTEM, LIGHTNING PROTECTION, NURSE CALL, VOICE
 AND DATA.
  
  
 ROBERT LECKY, CBO
 PLANS EXAMINER