2012-03-28 15:37:04 | BUILDING PLAN REVIEW |
| PERMIT: 12030309 |
| ADD: 2047 PALM BEACH LAKES |
| CONT: LEIGHTON MCGINN |
| TEL: (561)722-9697 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) LIFE SAFETY PLAN UNDER THE HEADING BUILDING CODE |
| REQUIREMENTS PLEASE PROVIDE A COMPLIANCE METHOD 2007/09 |
| EXISTING BUILDING CODE 101.5. |
| |
| 2) SHEET A1 INDICATES THREE 1 HOUR FIRE RATED WALLS BUT |
| THERE IS NO WALL TAG IDENTIFYING MARKERS FOR SUCH WALLS |
| FOUND ON THIS SHEET. |
| |
| 3) SHEET A1 THE DOORS LOCATED WITHIN THE FIRE RATED |
| WALLS DO NOT SHOW ON THE DOOR SCHEDULE SHEET A4. |
| |
| 4) SHEET A1 THE HANDICAPPED TOLIET ROOM # 109 IT |
| APPEARS THE DOOR IS SWINGING OVER THE CLEAR FLOOR SPACE |
| FOR THE LAV AND WATER CLOSET. 11-4.22.2(1). |
| |
| 5) SHEET A1 INDICATES THE USE OF MEDICAL GAS PLEASE |
| PROVIDE THE AMOUNT OF COMPRESSED GAS (CUBIC FT) TO BE |
| BOTH USED AND STORED IN ROOM 134 TO SEE IF THIS MAY BE |
| CONSIDERED A HAZARDOUS LOCATION AND OR A CONTROLED AREA |
| REQUIRING A 1 HOUR SEPERATION. PLEASE PROVIDE MSDS |
| SHEETS FOR ALL GASSES.2007/09 FBC-B 414.2 & 414.2.1 |
| CONSTRUCTION REQUIREMENTS. |
| |
| 6) 421.3.12 FIRE ALARM SYSTEMS. 421.3.12.1 A FIRE ALARM |
| ANNUNCIATOR PANEL SHALL BE PROVIDED PER FACILITY OR |
| BUILDING AT A LOCATION THAT IS CONSTANTLY ATTENDED |
| DURING THE FACILITY'S HOURS OF OPERATION AND SHALL |
| ANNUNCIATE A FIRE ALARM FROM ANY MANUAL OR AUTOMATIC |
| FIRE ALARM DEVICE. THE PANEL SHALL INDICATE THE ZONE OF |
| ACTUATION OF THE ALARM, AND THERE SHALL BE A TROUBLE |
| SIGNAL INDICATOR. EACH SMOKE COMPARTMENT SHALL BE |
| ANNUNCIATED AS A SEPARATE FIRE ALARM ZONE. A FIRE ALARM |
| SYSTEM ZONE SHALL NOT INCLUDE ROOMS OR SPACES IN OTHER |
| SMOKE COMPARTMENTS AND SHALL BE LIMITED TO A MAXIMUM |
| AREA OF 22,500 SQUARE FEET (2090 M2). |
| |
| 7) NEITHER IN THE STRUCTURAL NOR MECHANICAL PLANS ARE |
| THERE ANCHORING DETAILS FOR THE FOUR ROOF TOP PACKAGE |
| UNITS NOR TIE DOWN DETAILS FOR THE PACKAGE UNITS TO |
| CURB. |
| 2007/09 FBC-B 1609 . |
| |
| 8) A ROOFING CONTRACTOR IS SIGNED ON FOR THE ROOFING |
| SUB-PERMIT AND ROOFING NOA 07-1203.01 FOR GAF RUBEROID, |
| MODIFIED BITUMEN ROOF SYSTEMS FOR WOOD DECK, BUT NO |
| SUB-SYSTEM WAS INDICATED WITHIN THE 30 PAGE REPORT. |
| PLEASE NOTE THE ROOFING SUB-SYSTEMS GENERALLY HAVE A |
| MAXIMUM DESIGN PRESSURE FROM 45-60 PSF AND A GENERAL |
| LIMITATION # 7 WHICH DOES ALLOW FOR ENHANCED FASTENING |
| IN ZONES 2 & 3 BY A FLORIDA REGISTERED PROFESSIONAL |
| ENGINEER OR REGISTERED ARCHITECT. |
| |
| 9) SHEET A3 INDICATES THE USE OF SCUPPERS AND OVERFLOW |
| SCUPPERS, THIS SHEET PROVIDES THE HEIGHT OF THE |
| SCUPPERS AND OVER FLOW BUT NOT THE WIDTH, FBC-B |
| 1503.4.3 OVERFLOW SCUPPERS SHALL BE SIZED IN ACCORDANCE |
| WITH THE FBC-PLUMBING, THERE ARE TWO SCUPPERS AND ONLY |
| ONE OVERFLOW, PROVIDE CALCULATIONS FOR SIZING. |
| |
| 10) SHEEET A1 DOES NOT PROVIDE A LIFE SAFETY PLAN NOR |
| EXIT SIGNAGE REQUIRED BY FBC-B 1006.3 BUT E2 DOES |
| PROVIDE THE EXIT SIGNAGE INDICATING EXITING THROUGH TWO |
| STORAGE AREA, |
| SOILED HOLDING ROOM 114 AND MATERIALS MANAGEMENT AND |
| DELIVERS ROOM 131. FBC-B 1014.2 EGRESS SHALL NOT PASS |
| THROUGH STORAGE ROOMSCLOSETS OR SPACES USED FOR SIMILAR |
| PURPOSES. |
| |