2012-03-28 15:37:04BUILDING PLAN REVIEW
 PERMIT: 12030309
 ADD: 2047 PALM BEACH LAKES
 CONT: LEIGHTON MCGINN
 TEL: (561)722-9697
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) LIFE SAFETY PLAN UNDER THE HEADING BUILDING CODE
 REQUIREMENTS PLEASE PROVIDE A COMPLIANCE METHOD 2007/09
 EXISTING BUILDING CODE 101.5.
  
 2) SHEET A1 INDICATES THREE 1 HOUR FIRE RATED WALLS BUT
 THERE IS NO WALL TAG IDENTIFYING MARKERS FOR SUCH WALLS
 FOUND ON THIS SHEET.
  
 3) SHEET A1 THE DOORS LOCATED WITHIN THE FIRE RATED
 WALLS DO NOT SHOW ON THE DOOR SCHEDULE SHEET A4.
  
 4) SHEET A1 THE HANDICAPPED TOLIET ROOM # 109 IT
 APPEARS THE DOOR IS SWINGING OVER THE CLEAR FLOOR SPACE
 FOR THE LAV AND WATER CLOSET. 11-4.22.2(1).
  
 5) SHEET A1 INDICATES THE USE OF MEDICAL GAS PLEASE
 PROVIDE THE AMOUNT OF COMPRESSED GAS (CUBIC FT) TO BE
 BOTH USED AND STORED IN ROOM 134 TO SEE IF THIS MAY BE
 CONSIDERED A HAZARDOUS LOCATION AND OR A CONTROLED AREA
 REQUIRING A 1 HOUR SEPERATION. PLEASE PROVIDE MSDS
 SHEETS FOR ALL GASSES.2007/09 FBC-B 414.2 & 414.2.1
 CONSTRUCTION REQUIREMENTS.
  
 6) 421.3.12 FIRE ALARM SYSTEMS. 421.3.12.1 A FIRE ALARM
 ANNUNCIATOR PANEL SHALL BE PROVIDED PER FACILITY OR
 BUILDING AT A LOCATION THAT IS CONSTANTLY ATTENDED
 DURING THE FACILITY'S HOURS OF OPERATION AND SHALL
 ANNUNCIATE A FIRE ALARM FROM ANY MANUAL OR AUTOMATIC
 FIRE ALARM DEVICE. THE PANEL SHALL INDICATE THE ZONE OF
 ACTUATION OF THE ALARM, AND THERE SHALL BE A TROUBLE
 SIGNAL INDICATOR. EACH SMOKE COMPARTMENT SHALL BE
 ANNUNCIATED AS A SEPARATE FIRE ALARM ZONE. A FIRE ALARM
 SYSTEM ZONE SHALL NOT INCLUDE ROOMS OR SPACES IN OTHER
 SMOKE COMPARTMENTS AND SHALL BE LIMITED TO A MAXIMUM
 AREA OF 22,500 SQUARE FEET (2090 M2).
  
 7) NEITHER IN THE STRUCTURAL NOR MECHANICAL PLANS ARE
 THERE ANCHORING DETAILS FOR THE FOUR ROOF TOP PACKAGE
 UNITS NOR TIE DOWN DETAILS FOR THE PACKAGE UNITS TO
 CURB.
 2007/09 FBC-B 1609 .
  
 8) A ROOFING CONTRACTOR IS SIGNED ON FOR THE ROOFING
 SUB-PERMIT AND ROOFING NOA 07-1203.01 FOR GAF RUBEROID,
 MODIFIED BITUMEN ROOF SYSTEMS FOR WOOD DECK, BUT NO
 SUB-SYSTEM WAS INDICATED WITHIN THE 30 PAGE REPORT.
 PLEASE NOTE THE ROOFING SUB-SYSTEMS GENERALLY HAVE A
 MAXIMUM DESIGN PRESSURE FROM 45-60 PSF AND A GENERAL
 LIMITATION # 7 WHICH DOES ALLOW FOR ENHANCED FASTENING
 IN ZONES 2 & 3 BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER OR REGISTERED ARCHITECT.
  
 9) SHEET A3 INDICATES THE USE OF SCUPPERS AND OVERFLOW
 SCUPPERS, THIS SHEET PROVIDES THE HEIGHT OF THE
 SCUPPERS AND OVER FLOW BUT NOT THE WIDTH, FBC-B
 1503.4.3 OVERFLOW SCUPPERS SHALL BE SIZED IN ACCORDANCE
 WITH THE FBC-PLUMBING, THERE ARE TWO SCUPPERS AND ONLY
 ONE OVERFLOW, PROVIDE CALCULATIONS FOR SIZING.
  
 10) SHEEET A1 DOES NOT PROVIDE A LIFE SAFETY PLAN NOR
 EXIT SIGNAGE REQUIRED BY FBC-B 1006.3 BUT E2 DOES
 PROVIDE THE EXIT SIGNAGE INDICATING EXITING THROUGH TWO
 STORAGE AREA,
 SOILED HOLDING ROOM 114 AND MATERIALS MANAGEMENT AND
 DELIVERS ROOM 131. FBC-B 1014.2 EGRESS SHALL NOT PASS
 THROUGH STORAGE ROOMSCLOSETS OR SPACES USED FOR SIMILAR
 PURPOSES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved