Plan Review Notes
Plan Review Notes For Permit 12030147
Permit Number 12030147
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2013-04-17 15:44:357670 OKEECHOBEE BOULEVARD
 PERMIT #12030147
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A1.1: PANIC/FIRE EXIT HARDWARE IS NEEDED IN
 ASSEMBLY OCCUPANCIES WHERE THE DOOR SERVES 50 OR
 PERSONS. DOOR #100, 101, 102, 107 & 108 WILL REQUIRE
 PANIC/FIRE EXIT HARDWARE. CURRENTLY THE SPECIFICATIONS
 DO NOT INDICATE THIS TYPE OF HARDWARE FOR THESE DOORS.
  
 SHEET A1.2: PANIC/FIRE EXIT HARDWARE IS NEEDED IN
 ASSEMBLY OCCUPANCIES WHERE THE DOOR SERVES 50 OR
 PERSONS. DOOR #201, 214, 218, 220, 223 & 224 WILL
 REQUIRE PANIC/FIRE EXIT HARDWARE. CURRENTLY THE
 SPECIFICATIONS DO NOT INDICATE THIS TYPE OF HARDWARE
 FOR THESE DOORS.
  
 SHEET E2-3: AN EXIT SIGN IS NEEDED AT THE SECONDARY
 EGRESS DOOR IN BREAKROOM #307.
  
 ELECTRICAL DRAWINGS: THE FIRE ALARM SYSTEM WILL NEED TO
 BE EQUIPPED WITH VOICE EVACUATION CAPABILITIES FOR AN
 ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD GREATER THAN
 300 PERSONS. PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES (REFERENCE SECTION 12.3.4.3.3 OF FLORIDA
 FIRE PREVENTION CODE - NFPA 101). PROVIDE A
 PRE-RECORDED FIRE ALARM EVACUATION MESSAGE NOTIFYING
 OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN THE
 BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE
  
 INSPECTOR NOTES: THE BUILDING IS FUNCTIONING AS A MIXED
 OCCUPANCY (NON-SEPARATED ASSEMBLY AND BUSINESS) THAT
 WILL NEED A FIRE ALARM SYSTEM WITH VOICE EVACUATION AND
 PANIC/FIRE EXIT HARDWARE ON EGRESS DOORS.