2012-12-04 17:32:05REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2010
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. NOT COMPLIED. THE 8X8 EXHAUST DUCT PENETRATING THE
 SHAFT ENCLOSURE ON PAGE M2-2 IS MISSING A FIRE/SMOKE
 DAMPER. SEE DRAWING MARK-UP IN PROJECTDOX FOR EXACT
 LOCATION.
  
 2. OK
  
 3. OK
  
 4. OK
  
 5. NOT COMPLIED. THE UPER DETAIL FOR THE STAND CALLS
 FOR GALVANIZED STEEL PIPE SUPPORTS, WHILE THE LOWER
 DETAIL CALLS FOR A PRE-MANUFACTURED STAND. WHICH IS
 CORRECT? IF A PRE-MANUFACTURED STAND IS TO BE USED,
 PROVIDE THE ACTUAL PRODUCT APPROVAL FOR THE STAND,
 APPROVED IN WRITING BY THE ENGINEER FOR THIS PROJECT
 PER FBC-B 106.3.3.
  
 6. NOT COMPLIED. SHOW ALL DUCT MOUNTED SMOKE DETECTORS
 ON THE MECHANICAL SHEETS. CODE COMPLIANCE OF THE
 DETECTOR LOCATION CANNOT BE DETERMINED BY SHOWING
 DETECTORS ON AN ELECTRICAL SHEET WHICH DOES NOT SHOW
 THE HVAC DISTRIBUTION SYSTEM. FBC-M 606.2.1 AND FBC-B
 106.1.
  
 7. NOT COMPLIED. SEE COMMENT #6 ABOVE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: