| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| *****APPROVED WITH PROVISIONS - SUBMIT REVISION***** |
| |
| REPEAT COMMENT: SHEET LS1-1: UPDATE THE CODE LIST TO |
| REFERENCE THE 2010 EDITION OF THE FLORIDA FIRE |
| PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF BOTH |
| NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. |
| |
| PROVIDE COPY OF PROJECT SPECIFICATIONS AS REFERENCED BY |
| DOOR SCHEDULE. |
| |
| PROVIDE A SEATING/FURNITURE LAYOUT FOR THE MULTIPURPOSE |
| ROOM #206 AND CONFERENCE ROOM #208. |
| |
| ELECTRICAL DRAWINGS: THE FIRE ALARM SYSTEM WILL NEED TO |
| BE EQUIPPED WITH VOICE EVACUATION CAPABILITIES FOR AN |
| ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD GREATER THAN |
| 300 PERSONS. PROVIDE SPEAKER/STROBE NOTIFICATION |
| APPLIANCES (REFERENCE SECTION 12.3.4.3.3 OF FLORIDA |
| FIRE PREVENTION CODE ? NFPA 101). PROVIDE A |
| PRE-RECORDED FIRE ALARM EVACUATION MESSAGE NOTIFYING |
| OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN THE |
| BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE |
| BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR. |
| |
| REPEAT COMMENT: SHEET E2-2: ONLY TWO EXIT SIGNS |
| PROVIDED FOR ENTIRE FLOOR. |
| |
| REPEAT COMMENT: SHEET E2-3: ONLY TWO EXIT SIGNS |
| PROVIDED FOR ENTIRE FLOOR. |
| |
| WESLEY JOLIN |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE |
| |
| INSPECTOR NOTES: THE BUILDING IS FUNCTIONING AS A MIXED |
| OCCUPANCY (NON-SEPARATED ASSEMBLY AND BUSINESS) THAT |
| WILL NEED A FIRE ALARM SYSTEM WITH VOICE EVACUATION AND |
| PANIC/FIRE EXIT HARDWARE ON EGRESS DOORS. |