Plan Review Notes
Plan Review Notes For Permit 12030147
Permit Number 12030147
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2012-10-01 11:27:357670 OKEECHOBEE BOULEVARD
 PERMIT #12030147
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****APPROVED WITH PROVISIONS - SUBMIT REVISION*****
  
 REPEAT COMMENT: SHEET LS1-1: UPDATE THE CODE LIST TO
 REFERENCE THE 2010 EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF BOTH
 NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 PROVIDE COPY OF PROJECT SPECIFICATIONS AS REFERENCED BY
 DOOR SCHEDULE.
  
 PROVIDE A SEATING/FURNITURE LAYOUT FOR THE MULTIPURPOSE
 ROOM #206 AND CONFERENCE ROOM #208.
  
 ELECTRICAL DRAWINGS: THE FIRE ALARM SYSTEM WILL NEED TO
 BE EQUIPPED WITH VOICE EVACUATION CAPABILITIES FOR AN
 ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD GREATER THAN
 300 PERSONS. PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES (REFERENCE SECTION 12.3.4.3.3 OF FLORIDA
 FIRE PREVENTION CODE ? NFPA 101). PROVIDE A
 PRE-RECORDED FIRE ALARM EVACUATION MESSAGE NOTIFYING
 OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN THE
 BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
 REPEAT COMMENT: SHEET E2-2: ONLY TWO EXIT SIGNS
 PROVIDED FOR ENTIRE FLOOR.
  
 REPEAT COMMENT: SHEET E2-3: ONLY TWO EXIT SIGNS
 PROVIDED FOR ENTIRE FLOOR.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE
  
 INSPECTOR NOTES: THE BUILDING IS FUNCTIONING AS A MIXED
 OCCUPANCY (NON-SEPARATED ASSEMBLY AND BUSINESS) THAT
 WILL NEED A FIRE ALARM SYSTEM WITH VOICE EVACUATION AND
 PANIC/FIRE EXIT HARDWARE ON EGRESS DOORS.