Plan Review Notes
Plan Review Notes For Permit 12030147
Permit Number 12030147
Review Stop B
Sequence Number 2
Notes
Date Text
2012-10-01 15:41:29BUILDING PLAN REVIEW
 PERMIT: 12030147
 ADD: 7670 OKEECHOBEE BLVD
 CONT:TBD
 TEL: (561)###-####
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 NEW 3 STORY TYPE II-B SPRINKLERED BUILDING
  
 2ND REVIEW
 OCT. 01/ 2012
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 2ND REQUEST, LS1-1 & A1-1, THE PLANS INDICATE RATED
 TENANT SEPARATION WALLS THAT DOUBLE AS CORRIDOR WALLS,
 BUT WHERE THE TENANT SEPERATION WALLS CONTINUE AROUND
 THE VARIOUS COMMON ELEMENT ROOMS (RESTROOMS, ELECTRICAL
 AND OR MECHANICAL ROOMS) THE ONE HOUR RATING IS
 MISSING. 2007/09 FBC-B 708.1(7). THE EXCEPTION BETWEEN
 BUSINESS OCCUPANCIES UP TO 3,000 SQUARE FEET WITHOUT
 RATED TENANT SPERATION WALLS WOULD BE SUITES ON THE
 SAME SIDE OF A CORRIDOR WHERE THE TOTAL OF TWO OR MORE
 SUITES WOULD BE A TOTAL OF UNDER 3,000 SQUARE FEET. AS
 DEPICTED ON THE LS SHEET THE AREAS OF CONCERN ARE
 INDICATED WITHIN THE TENANT SPACE.
  
 3) 2ND REQUEST, LS1-1 & A1-1, THE PLANS ROOM TYPES,
 SOME OF THESE ROOM HAVE INCIDENTAL USE AREAS (TABLE
 508.2 INCIDENTAL USE AREAS) ( MECHANICAL AND OR STORAGE
 ROOM < 100 S F) ) AND NEED TO CONSTRUCT THE WALLS IN
 ACCORDANCE WITH 2007/09 FBC-B 508.2.2.1 (SMOKE
 PARTITIONS).
  
 4) COMPLIED.
  
 5A) 2ND REQUEST, SHEET LS1-2 & A1-2, PLANS NOW INDICATE
 THE ROOM USAGE AND THE CONFERENCE ROOM AREA OF 1440 SQ
 FT CREATES AN A-3 OCCUPANCY, THE COVER SHEET INDICATED
 A LOADING OF 15 SQUARE FEET PER PERSON, OR A OCCUPANT
 LOAD OF 96. THE 1440 SQUARE FEET CREATES AN ACCESSORY
 OCCUPANCY
 2007FBC-B 508.3.1 THAT WILL REQUIRE FIRE RATED
 CORRIDORS PER 2007 FBC-B TABLE 1017.1.
  
 5B) THE SAME HOLDS TRUE FOR THE MULTIPURPOSE ROOM #
 206, THIS ROOM IS APPROXIMATELY 2340 SQUARE FEET, BEING
 A MULTIPURPOSE ROOM AGAIN WE WILL BE TAKING THE WORST
 CASE SENARIO WITH 7 SQ FT PER PERSON, THIS ROOM WOULD
 ALSO BE CONSIDERED AN A-3 OCCUPANCY.
  
 5C) IN BOTH ROOMS PLEASE PROVIDE A FURNATURE PLAN THAT
 WILL REDUCE THE OCCUPANT LOADS AND BRING THE REQUIRED
 DOOR WIDTH AND STAIR WIDTH BACK INTO COMPLIANCE. 2007
 FBC-B 1005.1. PLEASE NOTE WITH THE OCCUPANT LOAD TAKEN
 AT 7 SQUARE FEET FOR THE CONFERENCE ROOM AND
 MULTI-PURPOSE ROOM WOULD CREATE AN OCCUPANT LOAD OF
 OVER 500 REQUIRING A THIRD EXIT, 2007 FBC-B TABLE
 1019.1.
  
 COMMENT FROM 1ST REVIEW.THE PLANS DO NOT INDICATE ROOM
 TYPES, SOME OF THESE ROOM MAY BE INCIDENTAL USE AREAS
 AND NEED TO CONSTRUCT THE WALLS IN ACCORDANCE WITH
 2007/09 FBC-B 508.2.2.1 (SMOKE PARTITIONS).
  
 6A) 2ND REQUEST. SHEET A1-1 THE ELEVATOR MACHINE ROOM
 DOES NOT INDICATE RATED WALLS 3006.4. PLEASE SHOW ALL
 FIRE AND OR SMOKE RATED WALLS ON A1-1, A1-2 AND A1-3
 SINCE THE ROOMS AND DOORS ARE IDENTIFIED. 106.1.2.
 ADDITIONAL DATA. INDICATE ALL FIRE RATED WALLS, SMOKE
 PARTITIONS ON THE A1 SHEETS FOR ALL THREE STORIES,
 THERE ARE MANY WALLS THAT DO NOT INDICATE FIRE RATED
 WALLS
  
 .6B) COMPLIED.
  
 7) COMPLIED.
  
 8) 2ND REQUEST, SHEET A2-1 THE PRE-ENGINEERED ROOF
 ACCESS HATCH REQUIRES EITHER A FL STATE APPROVAL OR
 MIAMI-DADE NOA, RULE 9N-3(31)(A).
  
 9) 2ND REQUEST, SHEET A2-1 THE PRE-ENGINEERED A/C
 STANDS WILL ALSO REQUIRE EITHER A FL APPROVAL OR
 MIAMI-DADE NOA. RULE 9N-3(31)(G).
  
 10) SHEET A2-1 INDICATES THREE ROOMS 2 WITH
 APRROXIMATELY 6'-0" IN HEIGHT THE THIRD APPROXIMATELY
 8'-0 IN HEIGHT, WHAT WILL THESE ROOMS BE USED FOR?
 FBC-B 1509.2.
  
 11) COMPLIED.
  
 12) 2ND REQUEST, RESPONCE NOTED. SHEET A4-1, A 4-2 &
 A4-3 DETAIL # 10 PLEASE PROVIDE PRODUCT
 SPECIFICATIONS.2007/09 FBC-B 1406.2.2 ARCHITECTURAL
 TRIM. ARCHITECTURAL TRIM THAT EXCEEDS 40 FEET (12 192
 MM) IN HEIGHT ABOVE GRADE PLANE SHALL BE CONSTRUCTED OF
 APPROVED NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED
 TO THE WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE
 BRACKETS.
  
 13) SEMI- COMPLIED. SHEET A4-1 & A4-3 DETAIL # 17
 GAURDRAILS SEE OPENING LIMITATION OF 4 INCHES 1013.3
 FBC-B.
  
 14) COMPLIED AS NOTED: ASSISSTANTS DESK.
  
 15) 2ND REQUEST, ONCE ALL THE FIRE & SMOKE RATED WALLS
 ARE IDENTIFIED THE DOOR SCHEDULE WILL NEED TO BE
 UPDATED. 2007/09 FBC-B TABLE 715.4.
  
 16) COMPLIED.
  
 17) S1-2 THIS STRUCTURE WILL REQUIRE A SPECIAL
 INSPECTOR WPB ADMINISTRATIVE CODE 109.3.7 BUILDINGS
 MORE THAN 2 STORIES IN HEIGHT, AND TILT WALL
 CONSTRUCTION. CONTACT KEN CONRAD FOR REQUIRED LICENSING
 AND FORMS AT 561-805-6666.
  
 18) COMPLIED.
  
  
  
 19) 2ND REQUEST, 106.3.3 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 20) 2ND REQUEST, COMPONENTS & CLADDING FBC-B 1609.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 21) COMPLIED AS NOTED, EXTERIOR GLAZING WILL BE LARGE
 MISSILE IMACT.
  
 22) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  