2012-04-17 16:09:01 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. PAGES M2-2 AND M2-3: DUCT PENETRATIONS OF THE SHAFT |
| ENCLOSURES ADJACENT TO THE ELEVATOR SHALL BE PROTECTED |
| BY FIRE AND SMOKE DAMPERS PER FBC-M 607.5.5. |
| |
| 2. PAGE M2-3: THERE IS A FOOTNOTE #3 POINTING AT THE |
| FRESH AIR DUCT FROM THE ROOF. HOWEVER, THERE IS NO TEXT |
| ON THIS PAGE ASSOCIATED WITH THIS FOOTNOTE. PLEASE |
| CLARIFY. FBC-B 106.1. |
| |
| 3. PAGE M2-3: AHU #14 RETURN DROPS ARE SHOWN ON FLOOR |
| PLAN AS EXHAUST DROPS. PLEASE CLARIFY. BALANCED RETURN |
| IS REQUIRED PER FBC-M 601.4. |
| |
| 4. PAGE M2-2: AHU #5 FRESH AIR MOTORIZED DAMPER IS NOT |
| SHOWN IN THE CORRECT LOCATION. SHOW THE MOTORIZED |
| DAMPER IN THE FRESH AIR DUCT PER FBC-B 13-409.AB.3.3. |
| |
| 5. PAGE M4-2 AND M4-2A KEY NOTE #4 REFERS TO A DETAIL |
| FOR THE CONDENSER STANDS ON PAGE M5-1. NO SUCH DETAIL |
| COULD BE FOUND ON THAT PAGE. PLEASE CLARIFY WHETHER |
| THESE CONDENSER STANDS ARE SITE BUILT WITH CUSTOM |
| ENGINEERING OR IF THEY ARE PRE-ENGINEERED, MANUFACTURED |
| STANDS. IF THE PRE-ENGINEERED STANDS ARE USED, A |
| PRODUCT APPROVAL FOR THE STANDS IS REQUIRED TO BE |
| SUBMITTED PER FAC RULE 9N-1. |
| |
| 6. PAGE M2-2: DUCT SMOKE DETECTOR REQUIRED IN SUPPLY |
| SIDE OF AHU #4 PER FBC-M 606.2.1. |
| |
| 7. PAGE M2-3: DUCT SMOKE DETECTOR REQUIRED IN SUPPLY |
| SIDE OF AHU #15 PER FBC-M 606.2.1. |
| |