Plan Review Notes
Plan Review Notes For Permit 12030147
Permit Number 12030147
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-04-06 13:43:367670 OKEECHOBEE BOULEVARD
 PERMIT #12030147
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: ALL CONSTRUCTION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. SMOKING SHALL BE PROHIBITED
 EXCEPT IN DESIGNATED AREAS OUTSIDE THE BUILDING. ALL
 INTERIOR CONSTRUCTION AREAS SHALL HAVE "NO SMOKING"
 SIGNS POSTED.
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL: PROVIDE BUILDING ADDRESS VISIBLE FROM THE
 STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING AND
 BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND
 SHALL CONTRAST THE BACKGROUND.
  
 GENERAL: PORTABLE FIRE EXTINGUISHERS SHALL HAVE A
 MINIMUM RATING OF 2A:10BC AND SHALL BE TAGGED BY A
 LICENSED FIRE EXTINGUISHER COMPANY.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: WHEN IDENTIFYING THE FIRE RATED WALLS WITH
 SIGNAGE OR STENCILING, THE CHARACTERS SHALL BE AT LEAST
 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 GENERAL: NO INTERIOR FINISH CLASSIFICATIONS INDICATED
 FOR WALL AND CEILING MATERIALS.
  
 SHEET C6: FIRE DEPARTMENT CONNECTION SHALL BE
 IDENTIFIED WITH A SIGN STATING, "NO PARKING - FIRE DEPT
 CONNECTION". THIS WILL CAUSE THE REMOVAL OF 1 OF 9
 PARKING SPACES.
  
 SHEET C6: CONFIRM THE FIRE DEPARTMENT CONNECTIONS AND
 FIRE HYDRANTS WILL BE PROVIDED WITH CLEARANCES OF 7?-6?
 TO THE FRONT AND SIDES AND 4? TO THE BACKSIDE PER
 SECTION 18.3.4.1 OF NFPA 1 FLORIDA EDITION.
  
 SHEET C6: PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES
 FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 SHEET C6: PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 SHEET C6: PROVIDE PERMANENT WEATHERPROOF SIGN MARKING
 THE FIRE DEPARTMENT CONNECTION AND IDENTIFY THE
 BUILDING BEING SERVED.
  
 SHEET LS1-1 AND FP1-0: UPDATE THE CODE LIST TO
 REFERENCE THE 2010 EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF BOTH
 NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. FIRE
 SPRINKLER DESIGN SHALL CONFORM TO THE 2007 EDITION OF
 NFPA 13.
  
 **SHEET LS1-1: THE BUILDING IS FUNCTIONING AS A
 NON-SEPARATED MULTIUSE OCCUPANCY. THE OCCUPANCY TYPE IS
 INDICATED AS BUSINESS; HOWEVER, MULTIPURPOSE ROOM #206
 AND CONFERENCE ROOM #208 ARE FUNCTIONING AS ASSEMBLY
 OCCUPANCIES.
  
 SHEET LS1-1: BOTH STAIR ENCLOSURES DISCHARGE INSIDE THE
 BUILDING. PER SECTION 7.7 (NFPA 101), NOT MORE THAN 50%
 OF THE EXITS ARE ALLOWED TO DISCHARGE INSIDE THE
 BUILDING.
  
 SHEET A7-1: PROVIDE THE DOOR SCHEDULE HARDWARE GROUP
 INFORMATION (LOCKS, LATCHES, CLOSERS, PANIC HARDWARE,
 ETC.)
  
 MECHANICAL: PROVIDE DUCT SMOKE DETECTORS FOR AIR
 SYSTEMS EXCEEDING 2000 CFM.
  
 ELECTRICAL: MONITOR FIRE SPRINKLER TAMPER SWITCHES,
 FLOW SWITCHES, AND CLEAN AGENT SUPPRESSION SYSTEM.
 PROVIDE/MONITOR TAMPER SWITCHES ON BACKFLOW PREVENTER.
  
 SHEET E2-2: ONLY TWO EXIT SIGNS PROVIDED FOR ENTIRE
 FLOOR.
  
 SHEET E2-3: ONLY TWO EXIT SIGNS PROVIDED FOR ENTIRE
 FLOOR.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  