2012-03-20 13:52:55 | 12030147 | | 7670 OKEECHOBEE BLVD | | NEW 3 STORY OFFICE BUILDING | | | | PROVIDE A LIGHTING DENSITY CALCULATION VERIFYING | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | REQUIREMENTS. FBC 13-415 ABC.5 | | A SEPARATE BRANCH CIRCUIT SHALL SUPPLY ELEVATOR CAR | | LIGHTS. NEC 620.22 | | PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING | | CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN | | PROVIDED FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS. | | NEC 110.26, 240.24, 408.17 | | OVERCURRENT DEVICES SHALL NOT BE LOCATED IN THE | | VICINITY OF EASILY IGNITABLE MATERIAL. SEE STORAGE ROOM | | #345. NEC 240.24 | | | | NOTE: | | SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE | | ALARM SYSTEM, VOICE AND DATA. | | A SEPARATE PERMIT AND PLANS WITH WIND LOAD ENGINEERING | | FOR POLES, BASES AND FIXTURES IS REQUIRED. | | | | | | ROBERT LECKY | | ELECTRIC PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | | | | | |
|