Plan Review Notes For Permit 12030145
Permit Number 12030145
Review Stop B
Sequence Number 1
Notes
Date Text
2012-03-12 11:46:35****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM
 /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF)
  
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4,
 PROVIDE CALCULATIONS.
  
 2. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%.
  
 3. PROVIDE APPROXIMATE SQUARE FOOT AREA OF STUCCO TO BE
 REPAIRED.
  
 4. THERE IS ANOTHER APPLICATION PENDING FOR WHAT
 APPEARS TO BE THE SAME SCOPE OF WORK. PLEASE ADDRESS.
  
  
  