2012-05-31 09:57:38 | ****CORRECTIONS**** |
| ****PLAN REVIEW IN PROGRESS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2007 |
| |
| **IF ALL OTHER TRADES PASS REVIEW, ITEM 2 CAN BE |
| ADDRESSED VIA EMAIL (ON ARCHITECT'S LETTERHEAD). PERMIT |
| WILL BE ISSUED WITH A PROVISO THAT SHEET LS1 BE |
| REVISED** |
| |
| 1. IMPACT FEES ASSESSMENT REQUIRED, 561-233-5025 FOR |
| MORE INFORMATION. |
| |
| 2. SHEET LS 1, PLEASE REVISE THE ALLOWABLE AREAS TO |
| INCLUDE THE FORMULA FOR AREA INCREASE FBC 506.1 WITH |
| ENOUGH INFORMATION TO CONFIRM ACCURACY. |
| |
| REVISE PLAN TO DESIGNATE THE VARIOUS TENANT SPACES AND |
| OCCUPANCY CLASSIFICATION. |
| |
| SEE FBC 506.3, A 3X SPRINKLER INCREASE IS FOR BUILDINGS |
| WITH ONE STORY ABOVE GRADE. AS THIS IS A THREE STORY |
| BUILDING, IT APPEARS THAT A 2X INCREASE SHOULD BE USED. |
| |
| SEE FBC 506.2, PLAN STATES THAT A 100% FRONTAGE (OPEN |
| AREA INCREASE) WAS USED TO DETERMINE AREA, BUT THE AREA |
| SHOULD BE REVISED AS THE REAR DOES NOT HAVE 30' TO |
| PROPERTY LINE AND DISTANCE TO PROPERTY LINE IS UNCLEAR |
| ON THE NORTH SIDE (SEE FBC 506.2.2). THE FORMULA |
| APPEARS TO ALLOW A 75% INCREASE IF THERE IS 30' OPEN |
| AREA AROUND THE ENTIRE PERIMETER, NOT 100%. |
| |
| IF YOU CANNOT COMPLY WITH THE BUILDING AREA LIMITATION |
| PER FBC TABLE 503 FOR THE WORST CASE (A3, 15,500 SF), |
| THE FORMULA SHOULD BE WEIGHTED FOR THE VARIOUS |
| OCCUPANCIES AND OCCUPANCY SEPARATION WILL BE REQUIRED |
| IN ADDITION TO TENANT SEPARATION, SEE FBC 506.4.1. |
| |
| |
| |