Plan Review Notes For Permit 12030117 |
Permit Number |
12030117 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-04-25 10:25:43 | PLANS DENIED | | 1) PROVIDE FRESH AIR CALCULATIONS PER SECTION | | 13-409.AB.3.3 | | 2) PROVIDE ENERGY CALCULATIONS PER SECTION 13- 470.AB.1 | | SIZING. | | 3) NOTES ON PLANS SAY SEE SHEET M-2 .NO SHEET M-2 WAS | | SUBMITTED | | 4) PROVIDE PRODUCT APPROVALS FOR OUTSIDE GRILL FOR BATH | | EXHAUST 106.3 FBC. | | 5) ELEVATOR EQUIPMENT ROOM AND STORAGE ROOM SHOW NEW | | DUCT NOT EXISTING . | | PAGE M-1 OF PLANS. | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|