Plan Review Notes
Plan Review Notes For Permit 12030117
Permit Number 12030117
Review Stop M
Sequence Number 2
Notes
Date Text
2012-04-25 10:25:43PLANS DENIED
 1) PROVIDE FRESH AIR CALCULATIONS PER SECTION
 13-409.AB.3.3
 2) PROVIDE ENERGY CALCULATIONS PER SECTION 13- 470.AB.1
 SIZING.
 3) NOTES ON PLANS SAY SEE SHEET M-2 .NO SHEET M-2 WAS
 SUBMITTED
 4) PROVIDE PRODUCT APPROVALS FOR OUTSIDE GRILL FOR BATH
 EXHAUST 106.3 FBC.
 5) ELEVATOR EQUIPMENT ROOM AND STORAGE ROOM SHOW NEW
 DUCT NOT EXISTING .
 PAGE M-1 OF PLANS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]