Date |
Text |
2012-04-25 17:14:18 | 12030117 |
| 1016 CLARE AVE. #4 |
| INTERIOR REMODEL FOR INDOOR SOCCER |
| |
| PLEASE SUBMIT AN ELECTRICAL PLAN. |
| |
| INCLUDE A RISER PLAN SHOWING THE NEW AND EXISTING |
| ELECTRIC SERVICE COMPONENTS WITH MAIN DISCONNECT, |
| SERVICE GROUNDING, CONDUIT SIZE AND TYPE, VOLTAGE, |
| CONDUCTOR SIZE AND TYPE ALL LOCATED ON THE PLAN. |
| INCLUDE A SUMMARY LOAD CALCULATION SHOWING EXISTING |
| ELECTRIC SERVICE CAN HANDLE THE NEW LOADS; VERIFY |
| SAFETY CLEARANCES AND ACCESS. NEC 110.26, 215.5 |
| PROVIDE PANEL SCHEDULES SHOWING RATING, SIZE AND WIRING |
| METHOD FOR THE NEW ELECTRICAL CIRCUITS. NEC 210.3 |
| SHOW SERVICE LOCATION ON THE PLAN. NEC 230.72 |
| SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE |
| CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES |
| AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL |
| FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3, |
| EXISTING BUILDING CODE 711.1 |
| PROVIDE AN INTERSYSTEM BONDING TERMINAL. NEC 250.94 |
| PROVIDE FOR GFCI PROTECTION FOR ANY PROPOSED VENDING |
| MACHINES. NEC 422.51 |
| GFCI PROTECTION IS REQUIRED FOR RECEPTACLES IN |
| BATHROOMS, OUTDOORS, AND ADJACENT TO SINKS. NEC 210.8 |
| PROVIDE SPECIFICATIONS ON LIGHT FIXTURES SHOWING |
| PROTECTION AGAINST DAMAGE. LUMINAIRES SUBJECT TO |
| PHYSICAL DAMAGE INSTALLED IN PLAYING AREAS AND |
| SPECTATOR SEATING AREAS SHALL BE PROTECTED FROM DAMAGE. |
| NEC 410.10(E) |
| VERIFY THE REQUIRED WORKING CLEARANCES AND DEDICATED |
| WORKING SPACE HAS BEEN PROVIDED FOR THE ELECTRICAL |
| EQUIPMENT AND PANEL BOARDS. NEC 110.26, 240.24, 408.17 |
| PROVIDE A MECHANISM TO GUARD THE PANEL BOARDS TO |
| PREVENT PHYSICAL DAMAGE IF LOCATED NEAR THE PLAYING |
| FIELDS. NEC 110.27 |
| SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE |
| ALARM SYSTEM, VOICE AND DATA. |
| |
| ROBERT LECKY |
| ELECTRICAL PLANS EXAMINER |
| [email protected] |
| 561-805-6718 |
| |