2012-04-19 14:37:12 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| |
| 1. COMMENTS FROM PREVIOUS CHECKLIST WERE PROPERLY |
| ADDRESSED WITH EXCEPTION OF IMPACT FEES. NEW COMMENTS |
| ARE BASED ON NEW INFORMATION PROVIDED. |
| |
| 2. PROVISO ITEM, FBC EXISTING BUILDING, INTERIOR |
| FINISHES (BOTH EXISTING AND NEW) TO COMPLY WITH FBC |
| TABLE 803.5 FOR ASSEMBLY OCCUPANCY. |
| |
| 3. FBC EXISTING BUILDING 912.4.1, FBC 1008.1.9, EACH |
| DOOR IN GROUP A WITH AN OCCUPANT LOAD OF 50 OR MORE |
| SHALL NOT BE PROVIDED WITH A LATCH OR LOCK UNLESS IT IS |
| PANIC HARDWARE OR FIRE EXIT HARDWARE, SEE ALSO |
| EXCEPTION FOR MAIN DOOR. PLEASE ADVISE, WHICH DOORS |
| WILL BE ALTERED AND IF EXTERIOR EXIT DOORS ARE TO BE |
| REPLACED, PROVIDE PRODUCT APPROVALS AND NOTE ON PLAN. |
| |
| 4. THE MAIN ENTRY IS NOT CLEAR. PLEASE PROVIDE |
| INFORMATION REGARDING HOW OCCUPANTS WILL ENTER THIS |
| SPACE, FBC 1008. IT APPEARS THAT THE AREA IN THE |
| COVERED PARKING MARKED GRAND STAIR IS THE MAIN ENTRANCE |
| TO BOTH THIS TENANT SPACE AS WELL AS THE ADJACENT |
| SPACES. |
| |
| 5. FBC EXISTING BUILDING 912.4.1, FBC 1008.1.2, DOORS |
| ARE TO SWING IN THE DIRECTION OF TRAVEL WHERE THE |
| OCCUPANT LOAD EXCEEDS 50. THE DOOR WHICH APPEARS TO BE |
| THE MAIN ENTRY, DOOR 1 TO THE VALET, DOES NOT SWING IN |
| THE DIRECTION OF EGRESS TRAVEL. THE NOTE WHICH STATES |
| THAT THIS IS TO BE MARKED AS NOT AN EXIT IS NOTED; |
| HOWEVER, IT APPEARS THAT THIS IS THE MAIN ENTRY FOR |
| THIS PORTION OF THE BUILDING, AND OCCUPANTS TEND TO |
| EXIT IN THE SAME MANNER IN WHICH THEY ENTERED. |
| |
| 6. FBC EXISTING BUILDING 912.4.1, FBC 1025.2, WIDTH OF |
| THE MAIN ENTRANCE IS TO ACCOMMODATE FIFTY PERCENT OF |
| THE OCCUPANT LOAD. PLEASE NOTE THAT, IF DOOR 1 TO VALET |
| AREA IS THE MAIN ENTRANCE, AND THE GRAND STAIR REWORKED |
| BY EXTENDING THE LANDING, IT APPEARS THAT IT MAY BE |
| POSSIBLE TO ADD EXIT DOORS TO THE LOBBY AREA TO |
| INCREASE EXIT CAPACITY. |
| |
| 7. FBC EXISTING BUILDING 912.4.1, FBC 1009, PLEASE |
| PROVIDE STAIR WIDTHS. PLEASE CONFIRM THAT ANY STAIRS |
| WHICH DO NOT SHOW RISER AND TREAD DIMENSIONS ARE IN |
| COMPLIANCE. REGARDING THE STAIRS WHICH HAVE A 7.25 RISE |
| RATHER THAN A 7 INCH RISE AS REQUIRED, THESE STAIRS MAY |
| REMAIN IN USE. HOWEVER, PLEASE REWORK STAIRS WHICH SHOW |
| A TREAD LESS THAN 11 INCHES. |
| |
| 8. PROVIDE THE WIDTH FOR THE EXIT RAMPS, FBC EXISTING |
| BUILDING 912.4.1, FBC 1010. |
| |
| 9. PLEASE REVISE THE OCCUPANT LOAD FOR THE SOCCER |
| FIELDS AND INCLUDE AN OCCUPANT LOAD FOR THE FUTURE |
| BASKETBALL COURT. THE OCCUPANT LOAD SHOULD INCLUDE THE |
| 12 PLAYERS, SUPPORT PARTICIPANTS SUCH AS SUBSTITUTES, |
| OFFICIALS, COACHES, AND A REASONABLE NUMBER OF |
| SPECTATORS. |
| |
| 10. FBC EXISTING BUILDING 912.4.1, ALL ELEMENTS IN THE |
| MEANS OF EGRESS SUCH AS HANDRAILS, GUARDRAILS ARE TO |
| COMPLY WITH FBC CHAPTER 10. IN LIEU OF REQUIRING |
| DETAILS FOR EVERY EXISTING ELEMENT, THIS WILL BE A |
| PROVISO ITEM. |
| |
| 11. IMPACT FEES MAY BE DUE TO PALM BEACH COUNTY. |
| 233-5025 FOR MORE INFORMATION. THE PLANS ARE TO BE |
| STAMPED AND THE RECEIPT PROVIDED. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT YOUR CONVENIENCE TO |
| DISCUSS. |
| |