Plan Review Notes For Permit 12030117 |
Permit Number |
12030117 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-03-14 12:21:19 | PLANS DENIED | | 1) PROVIDE PRODUCT APPROVALS FOR OUTSIDE AIR GRILLE, | | AND SIZE OF GRILLE. | | SECTION 106.3 FBC. | | 2) ELEVATOR EQUIPMENT ROOM AND STORAGE ROOM SHOW NEW | | DUCT | | PROVIDE DUCT AND GRILLE SIZE ON THE PLANS | | 3) PROVIDE TWO COPIES OF THE MANUFACTURERS INSTALLATION | | INSTRUCTIONS ON | | THE FIRE DAMPERS WITH THE PLANS 304.1 GENERAL 2007 FBC | | (M) | | 4) REFER TO SECTION 601.4 BALANCED RETURN AIR EXCEPTION | | #3 FOR | | STORAGE ROOM. | | 5) REFER TO SECTION 601.4 BALANCED RETURN AIR FOR LOBBY | | 2007 FBC (M) | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|